DELTA MCS-180 3U 0 Power Shelf

Installation, Operations and

Maintenance Manual

6-2

2. While connecting the battery cables inside the distribution module, make sure the system

is completely disenergized (that is, the AC lines are turned off and the battery cables are
disconnected at the battery end).

3. The system voltage (rectifier output voltage) is –48VDC. Connect the positive battery

cable(s) to the BATT + and connect the negative battery cable(s) to the BATT -.

6.7 Temperature and Alarm Connections

6.7.1 Battery Temperature Sensors

One (1) battery sensor cable is provided with each system. The connection method please refers to
section 5.4.

6.7.2 External Alarm Connections

1. Table 21 Alarm Terminal Block Pin Assignments

Alarm Description

ACF AC

Fail

MAJ Major
HVSD High

Voltage

Shutdown

HV High

Voltage

Alarm

LV Low

Voltage

Alarm

LVD Low

Voltage

Disconnect

FA Fuse

Alarm

MIN Minor

2. Each alarm connection is provided with a normally close relay contact. This contact is capable of

carrying 0.5 Amp DC at 30VDC on a continuous basis.

3. Warning: All external circuits connected to these alarm relay terminals must be secondary and

properly isolated from the incoming line.

6.8 Connect the PDU signal cables to the rear of the shelf which are mark “EXT. Breaker trip

signal I/P” connector.

The “FUSE ALM” LED on the front panel of ALU will light up when the breaker open.

6.9 AC High Voltage Aux. Relay output wiring

The connection point of “AC High Voltage Trigger Relay” which is on the rear of shelf will close when the
AC input voltage is higher than the setting value normally it’s open.