DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

4-3

4.2.5 ALU Alarm Signal Descriptions

MAJ: Major

Alarm

(1) 2 or above rectifiers fail.

(2) Temperature

sensor

disconnects.

(3) AC Low Voltage Alarm.

(4) AC High Voltage Alarm.

(5) LVDS Trip Alarm. (System equipped with PDU)

(6) Battery or Ambient over temperature. (System equipped with PDU)

(7) HVSD

Alarm.

(8) Breaker

Trip

Alarm.

MIN: Minor

Alarm

(1) One rectifier fail.

(2) Current

Limit

Alarm.

(3) DC High Voltage Alarm.

(4) DC Low Voltage Alarm.

HV:

The alarm condition exists when the DC output voltage is higher than the parameter setting.

LV:

The alarm condition exists when the DC output voltage is lower than the parameter setting.

AC Fail:

The alarm condition exists when the AC voltage is absent.

LVDS:

The alarm condition exists when the DC output voltage is lower than the threshold voltage.

(System equipped with PDU)

Fuse Fail: The alarm condition exists when the battery switch trip off or the DC Load output switch trip off.

4.2.6 Physical

Table 18 displays the ALU mechanical data.

Table 18 ALU Mechanical Data

Dimension Value

Height 5.2

in.

(132mm)

Depth 9.9

in.

(251.3mm)

Width 1.9

in.

(46.2mm)