DELTA MCS-1800 3U Power Shelf

Installation, Operations and

Maintenance Manual

4-5

Settings Description

Comment

Steps -

0.1VDC

AC High Voltage Alarm

Function
Default
Recovery
Steps


-

AC high voltage alarm threshold adjustment

- 264V
- 261V
- 1V

AC Low Voltage Alarm

Function
Default
Recovery
Steps


-

AC Low voltage alarm threshold adjustment

- 176V
- 179V
- 1V

Temperature Alarm

Function
Default
Steps


-

Battery Temperature alarm

- 104℉ (40℃)
- 1℃

Site ID

Function
Setting


-

Set identification number for this site

-

4 digits and number range is 0-9

Floating / Equalize charging
voltage

Function



-

Float / Equalize charging voltage

Default

- Float
-

54.3VDC (-48V System)

-

27.2VDC (+24V System)

- EQUALIZE
-

56.4VDC (-48V System)

-

28.2VDC (+24V System)

Steps -

0.1V

LVDS Trip Voltage

Function


-

Sets LVDS trip voltage

Default

- 42VDC

(-48V

System)

-

22VDC (+24V System)

Recovery

-

When one rectifier work normally and not in the

CL Mode

Steps -

0.1V

Compensation On/Off

Function


- Enable / Disable Temperature Compensation

feature

Setting
Default

- ON/OFF
- On

Compensation Volt. Range

Function
Default

Steps


-

To set Temperature Compensation Voltage

- -1.3VDC~+1.3VDC

(-48V

System)

- -0.7VDC~+0.7VDC

(+24V

System)

- 0.1V

Equalize Duration Time

Function


- To set the duration of equalizes charging after

AC recovery. This setting is active when battery
deeply discharge resulting from AC fail.

Default
Steps

- 1-10

hours

- 1

hour

Mains Recovery Charging
Current Limited


- When mains recovery to avoid the charging

current too large, CSU will limit the charging
current.

-

[ (IL+ Max. Cap.) / Parameter] / available SMR