Delta MCS-1800 User Manual
Page 8
DELTA MCS-1800 3U Power Shelf
Installation, Operations and
Maintenance Manual
2-3
Figure 1-1 shows a front view of shelf.
Environmental Data
System Environmental Data
Specification Value
Operating temperature
0℃ to +50℃
Storage temperature
-40℃ to +70℃
Humidity
0% to 95% RH
Altitude
-300 ft. to 10,000 ft.
Weight
Approximately 48 lbs.
Lightning/surge ANSI/IEEE
C62.41-1, and IEC 1000-4-5
Seismic
Bellcore GR-63-CORE, Zone 4
2.3.4 -48V System with Power Distribution and Rectifiers(MODUL NAME: ES48/90-JFAxx)
(1) AC Input:
175VAC ~ 275VAC, 36Amps. Max
(2) System Capacity:
90Amps. Max.
(3) Rectifier:
-48V/30A×1~3
(4) Control and Supervisory
(5) Load Distribution:
100A Breaker×4 @ Single Pole
(6) Low Voltage Disconnect Switch: 100A×1 @ Single Pole at Battery Side
Figure 1-1 shows a front view of shelf.
Environmental Data
System Environmental Data
Specification Value
Operating temperature
0℃ to +50℃
Storage temperature
-40℃ to +70℃
Humidity
0% to 95% RH
Altitude
-300 ft. to 10,000 ft.
Weight
Approximately 48 lbs.
EMI/FRI
FCC Part 15, Class B and CISPR 22, Class B
Lightning/surge ANSI/IEEE
C62.41-1, and IEC 1000-4-5
Seismic
Bellcore GR-63-CORE, Zone 4
Safety
CUL and UL Listed and Marked
2.4 Electrical Data
The system electrical data is provided in the following tables.
2.4.1 Input