DELTA MCS-1800 3U Power Sh elf

Installation, Operations and

Maintenance Manual

3-1

3 Power Supply Unit (PSU)

3.1 Description

This rectifier units are rated at full load when operated from high line. For Low operation, the output is

derated to half load. This derating is automatically activated from the Alarm Control Unit (ALU). However,
the rectifier can operate on a stand-alone basis, if this ALU is removed or nonfunctional.

Warning: In the absence of the ALU, the automatic derating of the rectifiers at Low Line is not effective.

Exceeding the 50% load limit at Low Line may damage the rectifiers.

The modular design provides the flexibility to configure and expand the system as the load demand

increases. Each rectifier unit is swappable with front access for ease of maintenance without system shutdown,
providing uninterrupted service.

The rectifier unit has an active power factor correction of greater than 0.99 for maximum AC utilization.

Each module is equipped with an AC switch located at the front of the module. Figure 3 shows a front view of
PSU.

Note: The equipment is only for installation in a Restricted Access Location.

The equipment is used on a stationary equipment/unit only.

3.2 Specifications

Detailed rectifier specifications are provided in the following sections.

3.2.1 Electrical

Detailed electrical specifications for the rectifier are provided in this section.

3.2.1.1 Input

Table 6 displays the rectifier input specifications.

Table 6 Rectifier Input Specifications

Specification Value

Input Voltage

90VAC to 275VAC, Single Phase, (during 176 to 150VAC
derated to 80% Load, during 150 to 90VAC derated to 50% Load)

Input Current

12 Amps at 176 VAC, Full Load

Line Frequency

45 to 65 Hz

Power Factor

>0.99, at 220 VAC Input, Full Load

THD

<5%, at 220 VAC Input, Full Load

Efficiency

>90%, Full Load (-48V Version)
>88%, Full Load (+24V Version)

Inrush Current

<12 Amps (peak), 220 VAC, Full Load, Cold Start

Start Time Delay
(Walk-In)

3 to 10 seconds

Protection Fuse