Delta MCS-1800 User Manual
Page 17
DELTA MCS-1800 3U Power Shelf
Installation, Operations and
Maintenance Manual
4-2
Settings Description
FL/EQU
- Function
- This button is used to manually select SMR into float or equalize state.
HVSD RST
- Function
- When SMRs shut down resulting from DC high voltage. This button is
used to reset alarm state.
SMR RST
- Function
System will detect RFA warning when SMRs are vacant or turned off.
However, if the button is pushed at this time, the system will stop
sending the warning.
Voltage/Current
- Function
This button is used to change the voltage or current of LED display.
Notice: When SMR turn off , the system will detect RFA warning in ES48/90-JFAxx.
When SMR vacant , the system will detect RFA warning in other system.
4.2.3 Indicators
Table 15 displays the ALU indicators.
Table 15 ALU Indicators
Indicator Color Function
Description
LED1
Green
FL
System Float State
LED2
Yellow
EQU
System Equalize State
LED3
Red
HV
DC High Voltage Alarm-Minor
LED4
Red
LV
DC Low Voltage Alarm-Minor
LED5 Yellow MIN System
Minor
Alarm
LED6 Red MAJ
System
Major
Alarm
LED7
Red
HVSD
High Voltage Shutdown (DC)
LED8
Red
AC FAIL
Loss of AC Input
LED9
Red
FUSE ALM DC Output or Breaker SW. Trip
LED10
Red
LVDS OPEN Low Voltage Disconnect Open
4.2.4 Relay Output
Table 16 displays the relay output.(Please refer to Figure 5)
Table 16 Relay Output
Relay
Function
Description
Relay
Function Description
Relay1
ACF AC
Failure
Relay5
LV
DC Low Voltage
Alarm-Minor
Relay2
MAJ Major
Alarm
Relay6
LVD
Low Voltage Disconnect
Open
Relay3
HVSD High
Voltage
Shutdown Relay7
FA
Breaker Trip
Alarm
Relay4
HV
DC High Voltage
Alarm-Minor
Relay8
MIN Minor
Alarm