Install system controller – Greenheck Melink IH3 Installation User Manual
Page 5

Melink Corporation (513) 965-7300 www.melinkcorp.com
Turn OFF the System Con-
troller power switch before
wiring. Also turn off the
breaker feeding this circuit.
Install System Controller
B
C
Wire Connections Inside System Controller
D
Retrofits:
It is not required to use
these output terminals if
there are other provisions
in place to control the
hood lights. Note that
output voltage will be the
same as the input voltage.
Tungston Output Rating:
8A @ 120V
5.4A @ 240V
115/230V
INPUT
L N G
L N G
115/230V (15A)
LIGHTS (OUTPUT)
New Construction & Retrofits:
Main Input Power
from Hood Light Circuit
115-230 VAC @ 50/60Hz; 17A Max
New Construction:
Outgoing Power to Hood Lights
Output Voltage Matches Input
15 Amps max
For both New Construction & Ret-
rofits, wire the System Controller
using the hood light circuit. The
circuit must be 115V to 230V, at
50-60Hz. Maximum input current
is 17A.
5
1
Turn Off Power Switch
Wire System Controller
ON
OFF
115V or 230V
Wire gauge per NEC; allowable size range is 16AWG to 12AWG.
- VCD-40 Extension Pin Kit 316SS (475290) (2 pages)
- 331-2856, 332-2856 - Siemens 6 Actuator (454206) (2 pages)
- 331-2976, 332-2976 - Siemens 4 Actuator (454202) (2 pages)
- 331-4551, 332-4551 - Siemens 3 Actuator (454201) (2 pages)
- Adjustable Pressure Controller (468292) (3 pages)
- 7800 Series Relay Modules (12 pages)
- Standard Control - MSSC (476372) (4 pages)
- NFB Series Actuators External Mount (464236 IOM) (2 pages)
- GND Series External Mount (473723) (4 pages)
- Amplifier for 7800 Series Relay Module (8 pages)
- APEX Curbs (462831) (4 pages)
- AMD-xx-TD Transmitter (35 pages)
- Blade Seal Repalcement (HCDR Series) (1 page)
- VCD (463384) (12 pages)
- BAPI Zone Pressure Touch (ZPT) Sensor (6 pages)
- VCD (463384) (10 pages)
- Blade Seal Replacement (HCD Series) (2 pages)
- BR Series - Counterweight Adjustment (469420) (4 pages)
- Leakage Rated Ceiling Radiation Dampers (475063 IOM). (32 pages)
- Canopy Hoods (452413 IOM) (36 pages)
- Clean-Out Port Kit (472428) (1 page)
- Centrifugal (CSW, BIDW, AFDW), Industrial (IPA, IPO, IPW) and Filtered Supply (LSF) (463687) (12 pages)
- Close Indicator Switch for Fire Dampers (474050) (1 page)
- Concrete Floor with Steel Deck Supplement (463562) (1 page)
- CRD-3XX and CRD-7XX Series for SP fans (452832) (2 pages)
- VCD (463384) (4 pages)
- VCD (463384) (8 pages)
- Single Side Retaining Angle (52 pages)
- DG / DGX with Pilot Ignition (463555 IOM) (Pre-2008) (48 pages)
- DG / DGX with Direct Spark (470652) (40 pages)
- Digital Temperature Interlock (474750 IOM) (Pre November 2012) (8 pages)
- DGK (468695) (20 pages)
- DG / DGX with Pilot Ignition (463555 IOM) (Pre-2008) (52 pages)
- Double Gland Axle Seal Replacement (1 page)
- Dock Arm Kit (475367) (4 pages)
- Duct Heaters Series IDHB and IDHC (478052) (8 pages)
- EHH-601D, Channel Installation (474643) (10 pages)
- EHH-601D, Channel Installation with VCD-40 Damper (474644) (8 pages)
- EHH-601D, Flange/Sleeve Installation (474641) (8 pages)
- GM Series (468391) (4 pages)
- EHH-601D, Flange/Sleeve Installation with VCD-40 Damper (474642) (8 pages)
- El-O-Matic E and P Series (12 pages)
- Energy Recovery Filter Hood System (8 pages)
- ERV-582/120 Curbs (460988) (4 pages)
- ESD-635D, Chanel Installation (474639) (10 pages)