Install system controller – Greenheck Melink IH3 Installation User Manual

Page 5

background image

Melink Corporation (513) 965-7300 www.melinkcorp.com

Turn OFF the System Con-
troller power switch before
wiring. Also turn off the
breaker feeding this circuit.

Install System Controller

B

C

Wire Connections Inside System Controller

D

Retrofits:

It is not required to use
these output terminals if
there are other provisions
in place to control the
hood lights. Note that
output voltage will be the
same as the input voltage.


Tungston Output Rating:
8A @ 120V
5.4A @ 240V

115/230V

INPUT

L N G

L N G

115/230V (15A)

LIGHTS (OUTPUT)

New Construction & Retrofits:

Main Input Power

from Hood Light Circuit

115-230 VAC @ 50/60Hz; 17A Max

New Construction:

Outgoing Power to Hood Lights

Output Voltage Matches Input

15 Amps max

For both New Construction & Ret-
rofits, wire the System Controller
using the hood light circuit. The
circuit must be 115V to 230V, at
50-60Hz. Maximum input current
is 17A.

5

1

Turn Off Power Switch

Wire System Controller

ON

OFF

115V or 230V

Wire gauge per NEC; allowable size range is 16AWG to 12AWG.