Install exhaust temperature sensor – Greenheck Melink IH3 Installation User Manual

Page 10

background image

L ≤ 24” (600mm)

L ≤ 24” (600mm)

Melink Corporation (513) 965-7300 www.melinkcorp.com

4

5

Hood 1 (Top View)

Install Exhaust Temperature Sensor

B

Install one (1) Temperature Sensor
per exhaust duct, if the length of the
duct is less than 24”. In most cases
this will mean one Temperature

Sensor per hood.



In some cases, this will mean two
Temperature Sensors per hood.




If the length of the duct is more than
24”, then install two Temperature
Sensors in order to obtain a better
average reading.

A

Duct Top View

L < 24” (600mm)

L ≥ 24” (600mm)

Hood 2 (Top View)

Hood 3 (Top View)

4

Determine Number of Sensors

Select Location for Mounting Sensor

Select a location for mounting each
Temperature Sensor. The tip of the
sensor should be inside the center
of the duct to sense the average
temperature. For most installations,
proceed with steps C-F on page
10. An alternate mounting proce-
dure is described in steps C-J on
pages 11 and 12.