Program Settings

B

System Parameters 

  

  

SY‐01 

Relay 1 Output 

Multi‐Select List  None 

Exhaust Temp Alarm 
Smoke 
Fan On 
MUA Damper 
Temperature Fault 
Optic Fault 
VFD Fault 
24/7 

Damper 

SY‐02 

Relay 2 Output 

Multi‐Select List 

SY‐03 

24VDC Output 1 

Multi‐Select List 

SY‐04 

24VDC Output 2 

Multi‐Select List 

SY‐05 

Digital Input 1 

Single Select List 

None 
Remote On/Off 
Remote On/Off w/ Enable 
Remote Enable/Disable 
50% Min Speed 
60% Min Speed 
70% Min Speed 
80% Min Speed 
90% Min Speed 
100% Min Speed 
External Fault Input 

None 

SY‐06 

Digital Input 2 

Single Select List 

SY‐07 

Digital Input 3 

Single Select List 

SY‐08 

Analog Output Function 

Single Select List  None, Average, Highest, Lowest 

None 

SY‐09 

Analog Output Source 

Multi‐Select List  List All Programmed Primary, Aux, and External 

None 

SY‐10 

Analog Input Function 

Multi‐Select List    

  

SY‐11 

Bypass Timer 

Single Select List  30 sec, 1 min, 5 min, 10 min, 20 min, 30 min, 1 hr,  10 minutes 

SY‐12 

Optic Hang Time 

Single Select List  5, 10, 15, 30, 60, 90, 120, 180, 240, 300 

15 seconds 

SY‐13 

Fan Speed Reporting Method 

Single Select List  VFD Feedback, Command Speed 

Feedback 

SY‐14 

Temperature Alarm Auto On 

Single Select List  Not Used, 100F, 125F, 150F, 200F, 250F, 300F  

200 

SY‐15 

Temperature Alarm Auto Off 

Single Select List  Not Used, On‐10, On‐20, On‐30,  

Not Used 

SY‐16 

Temperature Alarm Tone 

Single Select List  Yes or No 

No 

SY‐17 

Temperature Alarm Hoods to 
Activate 

Single Select List  All Hoods, Hood Group, Hood Only, None 

All 

SY‐18 

Data Log Sample Rate, Speed 

Single Select List  10s, 30s, 1min, 2min, 3min, 5min, 10min, 30min 

5 minutes 

SY‐19 

Data Log Sample Rate, Tempera‐ Single Select List  10s, 30s, 1min, 2min, 3min, 5min, 10min, 30min 

5 minutes 

SY‐20 

Data Log Sample Rate, Optics 

Single Select List  10s, 30s, 1min, 2min, 3min, 5min, 10min, 30min 

5 minutes 

SY‐21 

Auto On, Manual Off, Delay Time  Single Select List  10s, 30s, 1min, 2min, 3min, 5min, 10min, 30min 

2 minutes 

SY‐22 

Unit Display 

Single Select List  12H/F, 24H/F, 12H/C, 24H/C 

12H/F