of the cooking surface and the middle of the
hood filters. The Optic Sensors should be
mounted along that virtual line inside the
ends of the hood. (This is typically about 3”
from where the fitter bank meets the top of
the hood.) Also, the Optic Sensors must be
mounted directly across from each other.

Melink Corporation (513) 965-7300 www.melinkcorp.com

5
3

Install Optic Sensors

B

A

D

C

Make sure there are no obstructions at
least 10” (254mm) from where you need to
penetrate the top of the hood. Also, make
sure the location will not cause the Optic
Sensor beam to be obstructed by anything,
such as fire suppression piping.

To determine
where to install
the Optic Sen-
sors, imagine a
virtual line be-
tween the front

1-1/2”

3-1/4”

Approx. 3”

is typical.

Check Hood

Select Sensor Locations

Mark Hole Locations

Drill Holes in Hood

7

Then drill or punch a 1-1/2” (38mm) hole at
these same locations.

The hole locations need to be centered 3-1/4”
(83 mm) from the inside ends of the hood.
Drill a small pilot hole to mark these exact
locations.

17