Setting addresses – Greenheck Melink IH3 Installation User Manual

Page 28

background image

Melink Corporation (513) 965-7300 www.melinkcorp.com

5
3

Setting Addresses

B

A

D

C

Hood Controllers

Touchpad

Aux Touchpad, Aux Lighting

Controller, Aux Power Supply

Termination Resistor

10

28

Set the Hood Controller address by setting
the 10s and 1s address switches respectively.
Each Hood Controller must have a unique
address.

Set the Touchpad address through the Con-
figuration Menu. See Operations manual for
details. Each Touchpad must have a unique
address.

Set the address for the Aux Touchpad, Light-
ing Controller, and Power Supply by setting
their respective rotary switches. Each device
must have an address unique to its type. For
example, an Aux Touchpad and Aux Lighting
Controller can both be address 1, but two Aux
Touchpads cannot be address 1.

Set the Termination resistor to ON for the last
device plugged into each Hood Network
String. WARNING: DO NOT TURN ON ALL
TERMINATION RESISTORS IN THE
STRING OR THE COMMUNICATIONS WILL
NOT WORK PROPERLY.

10s Position

1s Position

`

`

`

ON

OFF