Set points menu - continued – Greenheck Microprocessor Controller v3.0 (469690) User Manual
Page 8
![background image](https://www.manualsdir.com/files/788091/content/doc008.png)
8
Supply Reset Limits
Supply
Min:055.0ºF
Supply
Max:090.0ºF
T
HIS
SCREEN
DISPLAYS
THE
MINIMUM
AND
MAXIMUM
SUPPLY
AIR
TEMPERATURE
.
This screen only appears if the room supply temp sensor is wired into terminals B4
and BC4 on the controller.
The supply air temp will integrate SLOWLY down (Pl loop) towards this minimum set
point to maintain room temperature. The supply air temp will integrate SLOWLY up (PI
loop) towards this maximum set point to maintain room temperature.
Cold coil set point
Normal
Mode:55.0ºF
Dehumidify:50.0ºF
Active set pt:55.0ºF
T
HIS
SCREEN
DISPLAYS
THE
TEMPERATURE
SET
POINTS
FOR
THE
COOLING
COILS
.
This screen only appears if a Cooling option was provided with the unit.
The Normal Mode set point is the after coil temperature the unit will maintain under
standard operation. If a Humidistat was provided with the unit, the Dehumidify set
point is the temperature the cooling coil will discharge on a call for dehumidification
from a humidistat.
The Active set pt is the temperature that the unit is currently trying to maintain off the coil.
Unoccupied room set
point
Heating:65.0ºF
Cooling:85.0ºF
T
HIS
SCREEN
DISPLAYS
THE
ROOM
SET
POINTS
WHICH
DICTATE
THE
UNIT
HEATING
AND
COOLING
OPERATION
DURING
UNOCCUPIED
MODE
.
This screen only appears if the “Cycle on Room” unoccupied mode was chosen
for the unit. A room sensor temp. must be wired into terminals B4 and BC4 on the
controller, and the unit must have a night setback damper.
In Unoccupied Mode when the temperature falls below the room Heating set point
(hysteresis = 5ºF), the supply fan and unit heating will turn on. Unit will discharge the
Supply Max temperature per the ‘Supply Reset Limits’ screen above until the room set
point is satisfied. Unit will then shut down. In Unoccupied Mode when the temperature
rises above the Cooling set point (hysteresis = 5ºF), the supply fan and unit cooling will
turn on. Unit will discharge the Supply Min temperature per the ‘Supply Reset Limits’
screen above until the room temperature set point is satisfied. Unit will then shut down.
Unit will energize
to maintain unocc
room set points.
Differential:5.0ºF
T
HIS
SCREEN
DISPLAYS
THE
D
IFFERENTIAL
SET
POINT
FOR
THE
HEATING
AND
COOLING
MODES
.
This screen only appears if the 7th character in the DDC Code is set to 1, meaning
the “Cycle on Room” unoccupied mode was chosen. Operation in “Cycle on Room”
unoccupied mode requires the room sensor be wired into terminals B4 and BC4 , and
a night setback damper in the unit.
This differential acts as a hysteresis to keep the heating and cooling from cycling too
often. For example, on a call for heating (room temp. set point - differential, 65.0ºF-
5.0ºF=60.0ºF) supply fan cycles on. Unit cycles off when the room temperature reaches
the Unoccupied room set point (65.0ºF, adjustable). For cooling, the differential is
added to the Unoccupied room set point (85.0ºF+5.0ºF=90.0ºF) to cycle supply fan
on. Unit cycles off when the room temperature reaches Unoccupied room set point
(85.0ºF).
SET POINTS MENU - continued
Room Set Point
Local set pt:72.0ºF
T
HIS
SCREEN
DISPLAYS
THE
SPACE
TEMPERATURE
SET
POINT
.
This screen only appears if the room supply temp sensor is wired into terminals B4
and BC4 on the controller.
The unit will reset the unit discharge temperature up and down to maintain the local
set point. If a BMS is interfaced with the controller, the user has the capability to
dictate the desired Room set point through the BMS. The screen will show a BMS
set point and an Active set point. The Active set point is the room temperature the
controller is currently trying to maintain.
Heater Lockout
Lockout heater when
outside air >:70.0ºF
Hysteresis=02.0ºF
T
HIS
CONTROLLER
WILL
LOCK
THE
HEATING
SECTION
OFF
WHEN
THE
OUTDOOR
AIR
TEMPERATURE
IS
ABOVE
THE
SET
POINT
(
FACTORY
DEFAULT
= 70ºF).
This screen only appears if a Heating option was provided with the unit.
A Hysteresis of 2ºF helps to avoid short cycling of the heater. The hysteresis is similar
to a deadband above and below the Lockout heater set point.
(Example: If Lockout = 70ºF, heating is locked out for outside air conditions above 72ºF
and enabled below 68ºF).