I/o setup menu - continued – Greenheck Microprocessor Controller v3.0 (469690) User Manual

Page 14

background image

14

Digital Input (ID2)
Wheel pressure switch
High

pressure=Closed

Status:Open

T

HIS

SCREEN

DISPLAYS

THE

ALARM

STATUS

MODE

OF

THE

ENERGY

RECOVERY

WHEEL

PRESSURE

SWITCH

.

When the Wheel pressure switch alarm is triggered, the wheel has excessive frost or
dirt build-up. The High pressure parameter allows the user to select Open or Closed
for the contact position that will trigger the alarm. Status displays the real time status
(open/closed) of the digital input.

Digital Input (ID3)
Wheel rotation alarm
Alarm:Closed
Status:Open

T

HIS

SCREEN

DISPLAYS

THE

ALARM

STATUS

MODE

OF

THE

ENERGY

RECOVERY

WHEEL

ROTATION

SENSOR

.

When the Wheel rotation alarm is triggered, the wheel has stopped rotating. Refer to
‘PROGRAM’ menu for wheel rotation alarm delay. Status displays the real time status
(open/closed) of the digital input.

Digital Input (ID4)
Unit ON/OFF control

Unit ON when:Closed

Status:Open

T

HIS

SCREEN

DISPLAYS

THE

STATUS

MODE

OF

THE

REMOTE

INPUT

FOR

UNIT

ON

/

OFF

CONTROL

.

The Unit ON when parameter allows the user to select Open or Closed for the contact
position that will energize the unit. Status displays the real time status (open/closed) of
the digital input.

Digital Input (ID5)
Exhaust proving switch
Alarm:Open
Status:Closed

T

HIS

SCREEN

DISPLAYS

THE

ALARM

STATUS

MODE

OF

THE

EXHAUST

FAN

.

When the Exhaust proving switch alarm is triggered, the fan is not seeing airflow and
the unit will shutdown and alarm. The Alarm parameter allows the user to select Open
or Closed for the contact position that will trigger the alarm. Status displays the real
time status (open/closed) of the digital input.

Digital Input (ID6)
Occupied/Unoccupied
Occupied

when:Open

Status:Closed

T

HIS

SCREEN

DISPLAYS

THE

ALARM

STATUS

OF

THE

O

CCUPIED

/U

NOCCUPIED

OPERATION

.

While in Input ID6 mode, (refer to ‘PROGRAM’ menu) the input from ID6 will send the
unit into occupied or unoccupied mode. If in BMS or Time Clock mode, a 24 VDC input
from ID6 will override the system operation from unoccupied (refer to ‘TIME CLOCK’
menu for actual override time period) to occupied (but not occupied to unoccupied)
mode for a specific override. The Occupied when parameter allows the user to select
Open or Closed for the contact position that will indicate Occupied operation. Status
displays the real time status (open/closed) of the digital input.

Digital Input (ID7)
Dirty filter switch
Alarm:Closed
Status:Open

T

HIS

SCREEN

DISPLAYS

THE

ALARM

STATUS

MODE

OF

THE

DIRTY

FILTER

SWITCH

.

The Alarm parameter allows the user to select Open or Closed for the contact position
that will trigger the alarm. Status displays the real time status (open/closed) of the
digital input.

Digital Input (ID8)
Compressor limits
Alarm:Open
Status:Closed

T

HIS

SCREEN

DISPLAYS

THE

ALARM

STATUS

MODE

OF

THE

COMPRESSORS

.

This screen only appears if DX cooling was provided in the unit.

The Alarm parameter allows the user to select Open or Closed for the contact position
that will trigger the alarm. Status displays the real time status (open/closed) of the
digital input. Based on factory defaults, the DX staging will lockout and alarm when the
Status is Open.

End of I/O setups