Access the PROGRAM menu by pressing

key. Scroll through the menu screens using the

keys.

The program button is used to setup the control loops for economizer, defrost, heating, cooling, and reheat
along with defaults for staging, supply reset, time delays, occupied mode, communications, set point source,
temperature scale, and changing passwords. Adjustments to these parameters should be performed by a
qualified technician. (A Level 2 password must be entered to alter any of the factory programming; factory
default is 9998).

T

HIS

SCREEN

CAN

BE

LOCKED

TO

PREVENT

TAMPERING

WITH

THE

SETTINGS

.

F

ROM

THE

FACTORY

,

ACCESS

IS

NOT

PASSWORD

PROTECTED

TO

ALLOW

QUICKER

START

-

UP

.

To set the password, go to the ‘PROGRAM’ menu by pressing the

button. Once

there, scroll down until you arrive at the Change Password screen. The ‘Level 2’
password protects the ‘Program’ menu.

***ACCESS DENIED***

Enter Password:0000

WRONG PASSWORD

Factory Setup

Consult factory

before altering

Economizer Controller

Integration:300s
Control Band:20ºF

T

HIS

SCREEN

ALLOWS

THE

INTEGRATION

TIME

FOR

THE

PI

CONTROL

OF

THE

ECONOMIZER

AND

THE

TEMPERATURE

BAND

AROUND

THE

SUPPLY

SET

POINT

TO

BE

ADJUSTED

.

This screen will only appear if an Economizer mode was selected with the unit.

This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Supply set pt ± Band. ie: 50° F ± 20° F

Economizer Setup
Econo on/off times
Minimum

ON:300s

Minimum

OFF:300s

T

HIS

SCREEN

ALLOWS

ADJUSTMENT

FOR

THE

M

INIMUM

ON/OFF

TIMES

FOR

THE

ECONOMIZER

.

This screen only appears if ON/OFF economizer was provided with the unit.

These minimum ON and OFF times prevent the energy wheel motor from short cycling
during economizer mode.

Supply fan cycling
defrost setup.

Fan off time:005min

Fan on time:030min

T

HIS

SCREEN

DISPLAYS

THE

ON/OFF

FAN

CYCLE

TIMES

FOR

THE

T

IMED

E

XHAUST

F

ROST

C

ONTROL

AND

ALLOWS

THE

USER

TO

ADJUST

THESE

PARAMETERS

.

This screen only appears if Timed Exhaust Frost Control was provided with the unit.

These ON and OFF times prevent the buildup of frost when the unit is in Timed Exhaust
frost control mode.

Cooling Controller

Integration:300s
Band:20ºF

T

HIS

SCREEN

DISPLAYS

THE

INTEGRATION

TIME

FOR

THE

PI

CONTROL

OF

THE

COOLING

MODE

,

AND

THE

TEMPERATURE

BAND

AROUND

THE

S

UPPLY

SET

POINT

.

This screen only appears if a Cooling option was provided with the unit.

This controller uses a Proportional + Integral type control. The integration time
programmed into the controller is to provide a smooth reaction to conditions, allowing
for less sporadic changes in discharge temperature. To speed up reaction time,
decrease the integration time. For slower reaction time, increase the integration time.
When making adjustments, make them in small increments, and test the system to
determine if the new setting is adequate prior to further adjustment. The band is the
range that the integration will occur between.
Range of Integration = Supply set pt ± Band. ie: 50° F ± 20° F

PROGRAM MENU