beautypg.com

Greenheck Microprocessor Controller v3.0 (469690) User Manual

Page 3

background image

3

UNIT SET POINTS

The cursor always begins in the upper left corner of the display.

__Supply air low limit alarm
when supply is less than:
35.0°F
Alarm delay: 030s

Supply air low limit alarm
when supply is less than:
32.0°F
Alarm delay: 030s

__Supply air low limit alarm
when supply is less than:
32.0°F
Alarm delay: 030s

Use the up

and down

buttons to scroll through the display screens. The

cursor must be in the upper left corner of the display to scroll through the screens.

Press

to move the cursor down for parameter adjustment.

Use the

keys to adjust the parameter up or down. Press

to move the

cursor to the next parameter, or to the upper left corner.

When finished, make certain the cursor is in the upper left corner. If the cursor is not in
the upper left corner, the changes made will not be saved. (The cursor must be in the
upper left corner to enable screen advancement).

If an alarm occurs, the

buttom will glow red, and a buzzer will sound if a remote display panel is connected to the

controller (if enabled).

**ALARM**

B1 SENSOR ERROR
OUTSIDE TEMPERATURE
ALARMED@-hr:min.mm/dd

…ALARM OPTIONS…

Press UP to review.
Press Esc to exit.
Press ALARM to RESET

SUPPLY AIR AL:

Indicates a loss of airflow in the supply fan

Alarm & Shutdown

EXHAUST AIR AL:

Indicates a loss of airflow in the exhaust fan

Alarm & Shutdown

DIRTY WHEEL AL:

Indicates a buildup of pressure across the energy recovery wheel

Alarm

WHEEL ROTATION AL:

Indicates a wheel rotation failure

Alarm

DIRTY FILTER AL:

Indicates a buildup of pressure across the filters

Alarm

COMPRESSOR TRIP AL:

Indicates a high or low refrigerant pressure

Alarm & Compressor Shutdown

AC LOCKOUT AL:

Indicates either the low pressure or high pressure switch are open

Alarm & Compressor Shutdown

SUPPLY LOW LIMIT AL:

Indicates a discharge temperature lower than the supply low limit
set point

Alarm & Shutdown

MB1 FAIL:

Indicates a failure of the outside air temperature sensor

Alarm

MB2 FAIL:

Indicates a failure of the supply air temperature sensor

Alarm

MB3 FAIL:

Indicates a failure of the after cooling coil air temperature sensor

Alarm

Example of parameter adjustment

Example of alarms

List of possible alarms

Step 1: Press the Alarm

button once. This will disable the buzzer and

display which alarms have occurred.

Step 2: Scroll down through the alarm screens if more than one has occurred.

Use the arrow buttons or alarm button to scroll through the alarms.

Step 3: Note which alarms occurred and at what time.

Step 4: Scroll down until the “Alarm Options” screen is displayed.

Step 5: Press the Esc

button to exit without resetting the alarms.

In this mode the unit will remain operational, as long as the alarm is
non-fatal.

Non-fatal alarms = dirty filters, sensor failure…

Fatal alarms = airflow loss…

Step 6: Press the Alarm

button to reset the alarms. If the alarm button

stops glowing red, the alarm has been cleared. No action is required.
(Sometimes a sensor can jump out of range for a short period of time,
causing an alarm. The sensor is probably OK, as long as the sensor
does not continually alarm and the displayed value looks reasonable).

Step 7: If the alarm signals again, the problem still exists and action needs to

be taken. Fix the condition that has caused the alarm.

OR