6
“STATUS LINE”
Hot Gas Reheat:000%
Heater
Control:000%
“STATUS LINE”
Energy recovery
wheel differential
pressure is: Normal
“STATUS LINE”
Preheat heater: OFF
End of status menu
T
HIS
SCREEN
DISPLAYS
THE
CURRENT
REHEAT
AND
HEAT
OPERATION
OF
THE
UNIT
.
Hot Gas Reheat only appears if provided with unit.
Hot Gas Reheat operation is on/off control displayed as a percent.
100% is ON and 000% is OFF
To override: ‘MANUAL OVERRIDE’ menu >Hot Gas Reheat Override
For Modulating Hot Gas Reheat Control:
000% is OFF and 001% HGRH is ON and the airflow damper is modulating
between 4 VDC and 10 VDC.
Heater Control displays the real-time percent heater output and is directly proportional
to a 0-10 VDC signal provided by the discharge temperature sensor.
To override: ‘MANUAL OVERRIDE’ menu >Heating Loop Override
Electric Heater: The Heater Control % is directly proportional to a 0-10 VDC signal
being sent to the SCR controller in the electric heater’s control center.
000% = 0 VDC = 0 kW output
100% = 10 VDC = Maximum kW output
Indirect Gas Furnace: The Heater Control % is directly proportional to a 0-10 VDC
signal being sent to the indirect gas furnace control board. The first stage is full ON at a
1% Heater Control. Once the Heater Control reaches 50%, the second stage modulates
between 50% and 100% output.
001 – 049%
First stage: ON, Second stage: OFF
050 – 100%
First stage: ON, Second stage: Modulating between
50%
and
100%
output
Hot Water Heater: The heating control valve (supplied by others) can either be 0-10 VDC
or 2-10 VDC depending upon what valve is installed. The user may have to adjust the
‘I/O SETUP’ menu so that a 0-100% heating correlates with a 2-10 VDC signal (0-10 VDC
is default).
To adjust: ‘I/O SETUP’ menu >Analog Output Y2
T
HE
UNIT
CONTAINS
A
WHEEL
PRESSURE
DROP
SENSOR
TO
INDICATE
WHETHER
THE
PRESSURE
ACROSS
THE
WHEEL
IS
N
ORMAL
OR
H
IGH
.
This screen only appears if a frost control method was provided.
A status of High is an indication of frost accumulation. The pressure set point is
adjustable on the wheel pressure switch.
T
HIS
SCREEN
INDICATES
WHETHER
THE
ELECTRIC
PREHEAT
FROST
CONTROL
IS
ON
OR
OFF
.
This screen only appears if Electric Preheat frost control was provided.
To override: ‘MANUAL OVERRIDE’ menu >Energy Recovery Wheel Preheater
UNIT STATUS MENU - continued
T
HIS
SCREEN
DISPLAYS
THE
COOLING
CONTROL
AS
A
PERCENTAGE
(
CONTINUED
)
The Compressor line indicates which compressor is ON
1
First
compressor
2
Second
compressor
1 2
Both compressors
To override: ‘MANUAL OVERRIDE’ menu >Cooling Loop Override
“STATUS LINE”
Cooling Control:000%
Compressor: ##