beautypg.com

Unit status menu - continued – Greenheck Microprocessor Controller v3.0 (469690) User Manual

Page 6

background image

6

“STATUS LINE”

Hot Gas Reheat:000%

Heater

Control:000%

“STATUS LINE”
Energy recovery
wheel differential
pressure is: Normal

“STATUS LINE”
Preheat heater: OFF

End of status menu

T

HIS

SCREEN

DISPLAYS

THE

CURRENT

REHEAT

AND

HEAT

OPERATION

OF

THE

UNIT

.

Hot Gas Reheat only appears if provided with unit.

Hot Gas Reheat operation is on/off control displayed as a percent.

100% is ON and 000% is OFF

To override: ‘MANUAL OVERRIDE’ menu >Hot Gas Reheat Override

For Modulating Hot Gas Reheat Control:

000% is OFF and 001% HGRH is ON and the airflow damper is modulating

between 4 VDC and 10 VDC.

Heater Control displays the real-time percent heater output and is directly proportional
to a 0-10 VDC signal provided by the discharge temperature sensor.
To override: ‘MANUAL OVERRIDE’ menu >Heating Loop Override

Electric Heater: The Heater Control % is directly proportional to a 0-10 VDC signal
being sent to the SCR controller in the electric heater’s control center.

000% = 0 VDC = 0 kW output

100% = 10 VDC = Maximum kW output

Indirect Gas Furnace: The Heater Control % is directly proportional to a 0-10 VDC
signal being sent to the indirect gas furnace control board. The first stage is full ON at a
1% Heater Control. Once the Heater Control reaches 50%, the second stage modulates
between 50% and 100% output.

001 – 049%

First stage: ON, Second stage: OFF

050 – 100%

First stage: ON, Second stage: Modulating between

50%

and

100%

output

Hot Water Heater: The heating control valve (supplied by others) can either be 0-10 VDC
or 2-10 VDC depending upon what valve is installed. The user may have to adjust the
‘I/O SETUP’ menu so that a 0-100% heating correlates with a 2-10 VDC signal (0-10 VDC
is default).

To adjust: ‘I/O SETUP’ menu >Analog Output Y2

T

HE

UNIT

CONTAINS

A

WHEEL

PRESSURE

DROP

SENSOR

TO

INDICATE

WHETHER

THE

PRESSURE

ACROSS

THE

WHEEL

IS

N

ORMAL

OR

H

IGH

.

This screen only appears if a frost control method was provided.

A status of High is an indication of frost accumulation. The pressure set point is
adjustable on the wheel pressure switch.

T

HIS

SCREEN

INDICATES

WHETHER

THE

ELECTRIC

PREHEAT

FROST

CONTROL

IS

ON

OR

OFF

.

This screen only appears if Electric Preheat frost control was provided.

To override: ‘MANUAL OVERRIDE’ menu >Energy Recovery Wheel Preheater

UNIT STATUS MENU - continued

T

HIS

SCREEN

DISPLAYS

THE

COOLING

CONTROL

AS

A

PERCENTAGE

(

CONTINUED

)

The Compressor line indicates which compressor is ON
1

First

compressor

2

Second

compressor

1 2

Both compressors

To override: ‘MANUAL OVERRIDE’ menu >Cooling Loop Override

“STATUS LINE”
Cooling Control:000%

Compressor: ##