Access the OVERRIDES menu through the Main Menu. Scroll through the menu screens using the

keys.

***ACCESS DENIED***

Enter Password:0000

WRONG PASSWORD

T

HIS

SCREEN

CAN

BE

LOCKED

TO

PREVENT

TAMPERING

WITH

THE

SETTINGS

.

F

ROM

THE

FACTORY

,

ACCESS

IS

NOT

PASSWORD

PROTECTED

TO

ALLOW

QUICKER

START

-

UP

.

To set the password, go to the ‘PROGRAM’ menu by pressing the

button. Once

there, scroll down until you arrive at the Change Password screen. The ‘Level 1’
password protects the ‘OVERRIDES’ Menu.

Manual override of
control loops
(Unit must be ON)

T

HE

O

VERRIDE

M

ENU

IS

USED

FOR

MANUAL

OVERRIDE

OF

THE

CONTROL

LOOP

.

THE

USER

CAN

OVERRIDE

THE

ENERGY

RECOVERY

WHEEL

OPERATION

.

This screen only appears if there is not a VFD operating the energy wheel.

When the wheel is in MANUAL mode, use the arrow buttons to turn the wheel ON or
OFF.

Energy recovery
wheel override
Wheel:AUTO
Wheel:OFF

THE

USER

CAN

OVERRIDE

THE

ENERGY

RECOVERY

WHEEL

OPERATION

.

This screen only appears if the Modulating Wheel Frost Control or Modulating Wheel
Economizer was provided with the unit.

When the wheel is in MANUAL mode, use the arrow buttons to change the % Speed to
vary the wheel rotational speed. The % Speed is directly proportional to a 0-10V signal
being sent to the energy wheel VFD.

Energy recovery
wheel override
Wheel:AUTO
%

Speed:000%

THE

USER

CAN

OVERRIDE

THE

COOLING

LOOP

OPERATION

.

This screen only appears if a cooling option was provided with the unit.

When the cooling loop override is in MANUAL mode, use the arrow buttons to vary the
% output.

Chilled Water Coil: Loop Output % is directly proportional to a 0-10 VDC or 2-10 VDC
signal.

000% = 0 VDC = Full Closed; 100% = 10 VCD = Full Open

000% = 2 VDC = Full Closed; 100% = 10 VCD = Full Open

2 Stage DX Coil: Loop Output displays compressor engagement as a percent.
000%

Compressor

OFF

050%

First Compressor ON

100%

First & Second Compressor ON

Second stage will NOT disengage until Loop Output is below 50%
First stage will NOT disengage until Loop Output is 0%

1 Stage DX Coil: Loop Output displays compressor engagement as a percent.
000%

Compressor

OFF

100%

Compressor

ON

In a single stage DX cooling system, the compressor engages when the Loop Output is
100%. Once the compressor is engaged, it will not disengage until the Loop Output is
0%.

Note: Damage can occur to compressors from short-cycling, therefore the controller
has built-in time delays which are effective upon each engagement of a compressor.

Cooling loop
override.
Cooling:AUTO
Loop

output:000%

MANUAL OVERRIDE MENU

To manualy override a function, change the status “AUTO” to “MANUAL”.