Manual override menu – Greenheck Microprocessor Controller v3.0 (469690) User Manual
Page 10
![background image](https://www.manualsdir.com/files/788091/content/doc010.png)
10
Access the OVERRIDES menu through the Main Menu. Scroll through the menu screens using the
keys.
***ACCESS DENIED***
Enter Password:0000
WRONG PASSWORD
T
HIS
SCREEN
CAN
BE
LOCKED
TO
PREVENT
TAMPERING
WITH
THE
SETTINGS
.
F
ROM
THE
FACTORY
,
ACCESS
IS
NOT
PASSWORD
PROTECTED
TO
ALLOW
QUICKER
START
-
UP
.
To set the password, go to the ‘PROGRAM’ menu by pressing the
button. Once
there, scroll down until you arrive at the Change Password screen. The ‘Level 1’
password protects the ‘OVERRIDES’ Menu.
Manual override of
control loops
(Unit must be ON)
T
HE
O
VERRIDE
M
ENU
IS
USED
FOR
MANUAL
OVERRIDE
OF
THE
CONTROL
LOOP
.
THE
USER
CAN
OVERRIDE
THE
ENERGY
RECOVERY
WHEEL
OPERATION
.
This screen only appears if there is not a VFD operating the energy wheel.
When the wheel is in MANUAL mode, use the arrow buttons to turn the wheel ON or
OFF.
Energy recovery
wheel override
Wheel:AUTO
Wheel:OFF
THE
USER
CAN
OVERRIDE
THE
ENERGY
RECOVERY
WHEEL
OPERATION
.
This screen only appears if the Modulating Wheel Frost Control or Modulating Wheel
Economizer was provided with the unit.
When the wheel is in MANUAL mode, use the arrow buttons to change the % Speed to
vary the wheel rotational speed. The % Speed is directly proportional to a 0-10V signal
being sent to the energy wheel VFD.
Energy recovery
wheel override
Wheel:AUTO
%
Speed:000%
THE
USER
CAN
OVERRIDE
THE
COOLING
LOOP
OPERATION
.
This screen only appears if a cooling option was provided with the unit.
When the cooling loop override is in MANUAL mode, use the arrow buttons to vary the
% output.
Chilled Water Coil: Loop Output % is directly proportional to a 0-10 VDC or 2-10 VDC
signal.
000% = 0 VDC = Full Closed; 100% = 10 VCD = Full Open
000% = 2 VDC = Full Closed; 100% = 10 VCD = Full Open
2 Stage DX Coil: Loop Output displays compressor engagement as a percent.
000%
Compressor
OFF
050%
First Compressor ON
100%
First & Second Compressor ON
Second stage will NOT disengage until Loop Output is below 50%
First stage will NOT disengage until Loop Output is 0%
1 Stage DX Coil: Loop Output displays compressor engagement as a percent.
000%
Compressor
OFF
100%
Compressor
ON
In a single stage DX cooling system, the compressor engages when the Loop Output is
100%. Once the compressor is engaged, it will not disengage until the Loop Output is
0%.
Note: Damage can occur to compressors from short-cycling, therefore the controller
has built-in time delays which are effective upon each engagement of a compressor.
Cooling loop
override.
Cooling:AUTO
Loop
output:000%
MANUAL OVERRIDE MENU
To manualy override a function, change the status “AUTO” to “MANUAL”.