Unit status menu – Greenheck Microprocessor Controller v3.0 (469690) User Manual
Page 5
5
Access the UNIT STATUS menu through the Main Menu. Scroll through the menu screens using the
keys. Screens with a dashed line border are dependent upon an optional accessory and may not
always appear.
“STATUS LINE”
System Status
hr:min:sec
mm/dd/yyyy
T
HE
S
TATUS
L
INE
DISPLAYS
WHICH
MODE
THE
UNIT
IS
IN
.
Possible modes include:
A. Initial Delay
J. Sys On-Dehumidifying
B. Opening Dampers
K. Sys On-Dehum & Reheat
C. Exhaust Fan Starting
L. Unoccupied-Unit Off
D. Supply Fan Starting
M. Unoccupied-Heating
E. System On
N. Unoccupied-Cooling
F. Defrost Mode Active
O. Manual Override!!
G. Sys On-Economizer
P. Remote Off
H. Sys On-Heating
Q. Press Alarm Button!
I.
Sys
On-Cooling
“STATUS LINE”
Outside:
000.
0º
F
Supply:
000.
0º
F
Cold Coil: 000. 0º F
“STATUS LINE”
Room:
000.
0º
F
“STATUS LINE”
Supply Fan:On
Exhaust Fan:On
T
HE
TEMPERATURES
ON
THIS
SCREEN
DISPLAY
REAL
-
TIME
CONDITIONS
FROM
THE
SENSORS
IN
THE
UNIT
.
After a period of inactivity (approximately 3 minutes), the controller will revert to this
screen.
T
HE
TEMPERATURE
ON
THIS
SCREEN
REPRESENTS
THE
REAL
-
TIME
CONDITIONS
BASED
ON
THE
SENSOR
IN
THE
ROOM
.
This screen only appears if the room supply temp reset sensor is wired into B4 and
BC4 on the controller.
T
HE
CONTROLLER
DISPLAYS
THE
RETURN
SIGNAL
THAT
IS
BEING
RECEIVED
FROM
THE
S
UPPLY
AND
E
XHAUST
FANS
.
On indicates the fan is running. In most modes of operation, both fans will be On. There
are three modes in which one fan may be Off while the other is On. 1) Start-up of the
unit, 2) Timed exhaust frost control, and 3) Unoccupied, 100% return air mode. Other
than these three modes, if one fan is Off and the other is On, there may be a problem.
“STATUS LINE”
Energy Recovery
Wheel: 000% Speed
“STATUS LINE”
Cooling Control:000%
Compressor: ##
E
NERGY
RECOVERY
WHEEL
OPERATION
IS
DISPLAYED
AS
A
PERCENT
.
If the unit does not contain a VFD on the wheel motor, then 0% = OFF; 100% = ON. If
the unit contains a VFD to modulate the wheel speed for frost control or economizer
operation, this screen will display the percentage directly proportional to the 0-10 VDC
signal being sent to the wheel VFD
0 VDC = 000%, 10 VDC = 100%
To override: ‘MANUAL OVERRIDE’ menu >Energy Recovery Wheel Override
T
HIS
SCREEN
DISPLAYS
THE
COOLING
CONTROL
AS
A
PERCENTAGE
.
This screen only appears if a cooling option is provided.
Chilled Water Coil: The Loop Output % is directly proportional to a 0-10 VDC signal
000% = 0 VDC - Full Closed; 100% = 10 VDC - Full Open
000% = 2 VDC - Full Closed; 100% = 10 VDC - Full Open
The cooling control valve can either be 0-10 VDC or 2-10 VDC depending upon the
valve installed. The user may need to adjust the I/O SETUP menu so that 0-100%
cooling correlates with a 2-10 VDC signal (0-10 VDC is default).
To adjust: ‘I/O SETUP’ menu> Analog Output Y3
DX Coil: Cooling Control displays compressor engagement as a percent
• 000% Compressors OFF
(1 or 2 compressor system)
• 050% First compressor ON
(2 compressor system)
• 100% First & second compressor ON
(2 compressor system)
First compressor ON
(1 compressor system)
UNIT STATUS MENU