Unit status menu – Greenheck Microprocessor Controller v3.0 (469690) User Manual

Page 5

background image

5

Access the UNIT STATUS menu through the Main Menu. Scroll through the menu screens using the

keys. Screens with a dashed line border are dependent upon an optional accessory and may not
always appear.

“STATUS LINE”

System Status
hr:min:sec
mm/dd/yyyy

T

HE

S

TATUS

L

INE

DISPLAYS

WHICH

MODE

THE

UNIT

IS

IN

.

Possible modes include:
A. Initial Delay

J. Sys On-Dehumidifying

B. Opening Dampers

K. Sys On-Dehum & Reheat

C. Exhaust Fan Starting

L. Unoccupied-Unit Off

D. Supply Fan Starting

M. Unoccupied-Heating

E. System On

N. Unoccupied-Cooling

F. Defrost Mode Active

O. Manual Override!!

G. Sys On-Economizer

P. Remote Off

H. Sys On-Heating

Q. Press Alarm Button!

I.

Sys

On-Cooling

“STATUS LINE”
Outside:

000.

F

Supply:

000.

F

Cold Coil: 000. 0º F

“STATUS LINE”
Room:

000.

F

“STATUS LINE”

Supply Fan:On
Exhaust Fan:On

T

HE

TEMPERATURES

ON

THIS

SCREEN

DISPLAY

REAL

-

TIME

CONDITIONS

FROM

THE

SENSORS

IN

THE

UNIT

.

After a period of inactivity (approximately 3 minutes), the controller will revert to this
screen.

T

HE

TEMPERATURE

ON

THIS

SCREEN

REPRESENTS

THE

REAL

-

TIME

CONDITIONS

BASED

ON

THE

SENSOR

IN

THE

ROOM

.

This screen only appears if the room supply temp reset sensor is wired into B4 and
BC4 on the controller.

T

HE

CONTROLLER

DISPLAYS

THE

RETURN

SIGNAL

THAT

IS

BEING

RECEIVED

FROM

THE

S

UPPLY

AND

E

XHAUST

FANS

.

On indicates the fan is running. In most modes of operation, both fans will be On. There
are three modes in which one fan may be Off while the other is On. 1) Start-up of the
unit, 2) Timed exhaust frost control, and 3) Unoccupied, 100% return air mode. Other
than these three modes, if one fan is Off and the other is On, there may be a problem.

“STATUS LINE”
Energy Recovery
Wheel: 000% Speed

“STATUS LINE”
Cooling Control:000%

Compressor: ##

E

NERGY

RECOVERY

WHEEL

OPERATION

IS

DISPLAYED

AS

A

PERCENT

.

If the unit does not contain a VFD on the wheel motor, then 0% = OFF; 100% = ON. If
the unit contains a VFD to modulate the wheel speed for frost control or economizer
operation, this screen will display the percentage directly proportional to the 0-10 VDC
signal being sent to the wheel VFD

0 VDC = 000%, 10 VDC = 100%

To override: ‘MANUAL OVERRIDE’ menu >Energy Recovery Wheel Override

T

HIS

SCREEN

DISPLAYS

THE

COOLING

CONTROL

AS

A

PERCENTAGE

.

This screen only appears if a cooling option is provided.

Chilled Water Coil: The Loop Output % is directly proportional to a 0-10 VDC signal

000% = 0 VDC - Full Closed; 100% = 10 VDC - Full Open

000% = 2 VDC - Full Closed; 100% = 10 VDC - Full Open

The cooling control valve can either be 0-10 VDC or 2-10 VDC depending upon the
valve installed. The user may need to adjust the I/O SETUP menu so that 0-100%
cooling correlates with a 2-10 VDC signal (0-10 VDC is default).

To adjust: ‘I/O SETUP’ menu> Analog Output Y3

DX Coil: Cooling Control displays compressor engagement as a percent

• 000% Compressors OFF

(1 or 2 compressor system)

• 050% First compressor ON

(2 compressor system)

• 100% First & second compressor ON

(2 compressor system)

First compressor ON

(1 compressor system)

UNIT STATUS MENU