beautypg.com

Time clock menu – Greenheck Microprocessor Controller v3.0 (469690) User Manual

Page 15

background image

15

T

HIS

SCREEN

CAN

BE

LOCKED

TO

PREVENT

TAMPERING

WITH

THE

SETTINGS

.

F

ROM

THE

FACTORY

,

ACCESS

IS

NOT

PASSWORD

PROTECTED

TO

ALLOW

QUICKER

START

-

UP

.

To set the password, go to the ‘PROGRAM’ menu by pressing the

button. Once

there, scroll down until you arrive at the Change Password screen. The ‘Level 1’
password protects the ‘TIME CLOCK’ menu.

CLOCK

hr:min:sec

(Day of week)

mm/dd/yyyy

T

HE

C

LOCK

SETUP

MENU

ALLOWS

THE

USER

TO

ADJUST

THE

TIME

,

DATE

,

AND

OCCUPIED

/

UNOCCUPIED

MODE

SETTINGS

.

User can also override the current occupied/unoccupied mode for a designated period
of time.

Time/Date/Day Setup
Press ENTER to reset
the internal clocks
time, date & day

Reset clock

Time-00:00:00
Date: 00/00/00 (m/d/y)
Day-NA

Set the time, date & day here. All three must be
set/reset at the same time. When the cursor is in the
upper left corner, press up or down to return to the
clock menu.

IMPORTANT!

User must select one of the three options for the Source in the

Unoccupied mode setup screen in the ‘PROGRAM’ menu. The Source represents the
means by which Occupied and Unoccupied modes are determined.

Option 1: Input ID6 – typically used with a remote time clock (Default)

Option 2: BMS – can be overridden by a separate input to ID6

Option 3: Internal Time Clock – can be overridden by a momentary input to ID6

Occ-Unocc Override
Current

Mode:Occ

Override

Time:060min

Override:No

C

URRENT

MODE

DISPLAYS

WHETHER

THE

UNIT

IS

IN

OCCUPIED

MODE

OR

UNOCCUPIED

MODE

.

(O

CC

= O

CCUPIED

, U

NOCC

= U

NOCCUPIED

)

This screen will only appear if the Occupied/Unoccupied ID6 function has been set
to ‘ON’ in the PROGRAM menu under Binary Input Enables.

The controller will allow the user to override from Unoccupied to Occupied mode, but
not vice versa. This can be performed by changing this screen to Yes, or it can also
be done through a momentary 24 VDC input to terminal ID6. After the Override Time
expires, the clock returns to the 7-day schedule.

Enable Occ/Unocc
Mon:Yes Tue:Yes Fri:Yes
Wed:Yes Thu:Yes Sat:Yes
Sun:Yes

The following screens only appear if Option 3, the Internal Time Clock function, has been enabled in the Program
Menu.

T

HIS

SCREEN

ALLOWS

THE

USER

TO

ENABLE

/

DISABLE

U

NOCCUPIED

MODE

FOR

EACH

DAY

OF

THE

WEEK

.

Selecting ‘No’ means the unit will operate in an Occupied mode only.
Selecting ‘Yes’ means the unit will operate in an Occupied mode and an Unoccupied
mode.

Occupied Unoccup
Mon 06:00 18:00
Tue 06:00 18:00
Wed 06:00 18:00

Enter the desired Occupied/Unoccupied start times for each day (24 hour time scale).

Occupied Unoccup
Thu 06:00 18:00
Fri 06:00 18:00

Enter the desired Occupied/Unoccupied start times for each day (24 hour time scale).

Access the

CLOCK SETUP

menu through the Main Menu. Scroll through the menu screens using the

keys.

***ACCESS DENIED***

Enter Password:0000

WRONG PASSWORD