Kfcc field connection checklist – Greenheck Kitchen Fan Control Center (475730) User Manual
Page 14
14
Kitchen Fan Control Center
KFCC Field Connection Checklist
Power to KFCC Cabinet and Lights
115 VAC power for controls (terminals H1, N1)
115 VAC power for hood lights, one per light circuit
(terminals H2, N2 | H3, N3 | H4, N4)
Connect lights, one per light circuit
(terminals B2, W2 | B3, W3 | B4, W4)
(Lights may be directly wired to switch)
Power for Fans
115/200/208/230/277 VAC power, single phase fans
from breaker (terminals L1, L2)
208/230/277/460/575 VAC power, three phase fans
from breaker (terminals L1, L2, L3)
115 VAC power for single phase to fan (contactor/
overload T3, terminal L1 is neutral)
208/230/277/460 VAC power to single phase fan
(contactor/overload T1, T3)
208/460/575 VAC power to three phase fan
(contactor/overload T1, T2, T3)
Fire System
Microswitch C, N.O., and N.C. (terminals C1, NO1,
NC1)
Spare Fire Relay
Spare, dry relay contact (terminals C3, NO3, NC3)
Spare, dry relay contact (terminals C4, NO4, NC4)
Switches - if equipped
Fan, 1-Speed (terminals S_H, S_; S_N is neutral if
lighted)
Fan, 2-Speed (terminals S_H, S_N, S_)
Light (terminals H2, B2 or H3, B3 or H4, B4; may be
directly wired to hood lights)
Thermal, heat only (terminals R, W1)
Thermal, supply only (terminals R, Y1)
Tempered (terminals R, W1, Y1)
Auto-Damper (terminals AD1, AD2, AD3, AD4, AD5)
MUA Interface - if equipped
To MUA Control Center (terminals R, G)
Power for Shunt Trip - if equipped
Shunt trip breaker coil (terminals STH, STN)
Extra Fire Relay (1) - if equipped
Spare, dry relay contact (terminals C9, NO9, NC9)
Spare, dry relay contact (terminals C10, NO10, NC10)
Extra Fire Relay (2) - if equipped
Spare, dry relay contact (terminals C11, NO11, NC11)
Spare, dry relay contact (terminals C12, NO12, NC12)
Extra Exhaust Relay (1) - if equipped
Spare, dry relay contact (terminals C7, NO7, NC7)
Spare, dry relay contact (terminals C8, NO8, NC8)
Extra Exhaust Relay (2) - if equipped
Spare, dry relay contact (terminals C15, NO15, NC15)
Spare, dry relay contact (terminals C16, NO16, NC16)
Extra Supply Relay (1) - if equipped
Spare, dry relay contact (terminals C5, NO5, NC5)
Spare, dry relay contact (terminals C6, NO6, NC6)
Extra Supply Relay (2) - if equipped
Spare, dry relay contact (terminals C13, NO13, NC13)
Spare, dry relay contact (terminals C14, NO14, NC14)
Exhaust Fan Failure Indicator - if equipped
Airflow switch (terminals AF1, AF2)
Supply Fan Failure Indicator - if equipped
Airflow switch (terminals AF3, AF4)
Status Lights (24 VAC or 120 VAC) - if equipped
Status light one (terminals SL1, SL2)
Status light two (terminals SL3, SL4)
Water Wash Control Panel (WWCP) Interface -
if equipped
From terminals 3 and 4 in WWCP (terminals S1H, S1)
Digital Style Temperature Interlock - if equipped
RTD sensor(s) (terminals T_-A, T_-B)
Thermostat Style Temperature Interlock - if equipped
Thermostat(s) (wired in parallel between terminals
T1-A, T1-B)
®