Kfcc field connection checklist – Greenheck Kitchen Fan Control Center (475730) User Manual

Page 14

background image

14

Kitchen Fan Control Center

KFCC Field Connection Checklist

Power to KFCC Cabinet and Lights

…

115 VAC power for controls (terminals H1, N1)

…

115 VAC power for hood lights, one per light circuit

(terminals H2, N2 | H3, N3 | H4, N4)

…

Connect lights, one per light circuit

(terminals B2, W2 | B3, W3 | B4, W4)
(Lights may be directly wired to switch)

Power for Fans

…

115/200/208/230/277 VAC power, single phase fans

from breaker (terminals L1, L2)

…

208/230/277/460/575 VAC power, three phase fans

from breaker (terminals L1, L2, L3)

…

115 VAC power for single phase to fan (contactor/

overload T3, terminal L1 is neutral)

…

208/230/277/460 VAC power to single phase fan

(contactor/overload T1, T3)

…

208/460/575 VAC power to three phase fan

(contactor/overload T1, T2, T3)

Fire System

…

Microswitch C, N.O., and N.C. (terminals C1, NO1,

NC1)

Spare Fire Relay

…

Spare, dry relay contact (terminals C3, NO3, NC3)

…

Spare, dry relay contact (terminals C4, NO4, NC4)

Switches - if equipped

…

Fan, 1-Speed (terminals S_H, S_; S_N is neutral if

lighted)

…

Fan, 2-Speed (terminals S_H, S_N, S_)

…

Light (terminals H2, B2 or H3, B3 or H4, B4; may be

directly wired to hood lights)

…

Thermal, heat only (terminals R, W1)

…

Thermal, supply only (terminals R, Y1)

…

Tempered (terminals R, W1, Y1)

…

Auto-Damper (terminals AD1, AD2, AD3, AD4, AD5)

MUA Interface - if equipped

…

To MUA Control Center (terminals R, G)

Power for Shunt Trip - if equipped

…

Shunt trip breaker coil (terminals STH, STN)

Extra Fire Relay (1) - if equipped

…

Spare, dry relay contact (terminals C9, NO9, NC9)

…

Spare, dry relay contact (terminals C10, NO10, NC10)

Extra Fire Relay (2) - if equipped

…

Spare, dry relay contact (terminals C11, NO11, NC11)

…

Spare, dry relay contact (terminals C12, NO12, NC12)

Extra Exhaust Relay (1) - if equipped

…

Spare, dry relay contact (terminals C7, NO7, NC7)

…

Spare, dry relay contact (terminals C8, NO8, NC8)

Extra Exhaust Relay (2) - if equipped

…

Spare, dry relay contact (terminals C15, NO15, NC15)

…

Spare, dry relay contact (terminals C16, NO16, NC16)

Extra Supply Relay (1) - if equipped

…

Spare, dry relay contact (terminals C5, NO5, NC5)

…

Spare, dry relay contact (terminals C6, NO6, NC6)

Extra Supply Relay (2) - if equipped

…

Spare, dry relay contact (terminals C13, NO13, NC13)

…

Spare, dry relay contact (terminals C14, NO14, NC14)

Exhaust Fan Failure Indicator - if equipped

…

Airflow switch (terminals AF1, AF2)

Supply Fan Failure Indicator - if equipped

…

Airflow switch (terminals AF3, AF4)

Status Lights (24 VAC or 120 VAC) - if equipped

…

Status light one (terminals SL1, SL2)

…

Status light two (terminals SL3, SL4)

Water Wash Control Panel (WWCP) Interface -
if equipped

…

From terminals 3 and 4 in WWCP (terminals S1H, S1)

Digital Style Temperature Interlock - if equipped

…

RTD sensor(s) (terminals T_-A, T_-B)

Thermostat Style Temperature Interlock - if equipped

…

Thermostat(s) (wired in parallel between terminals

T1-A, T1-B)

®