Summary table of configurations, Restoring factory settings – Delta Dore 610 TYBOX Installation User Manual
Page 9
- 17 -
Summary table of configurations
CF01
Correction of the temperature measured
by -4°C to +4°C in increments of 0.1°C (0 by default).
CF02
Automatic mode temperature display option
0 = Continuous set-point temperature display (by default)
1 = Room temperature display
CF03
Control of the Comfort temperature in heating mode
0 = controlled by the Tybox (by default) 1 = by each radiator or convector
CF04
Air conditioning function
0 = Not authorised (by default) 1 = Authorised
CF05
Circulator anti-seizing
0 = inactive (by default) 1 = active
CF06
Control time base
0 = 15 minutes (by default) 1 = 30 minutes 2 = 45 minutes
- 16 -
Restoring factory settings
Turn the knob to the position
Press the left button for 10 seconds
Press OK to confirm or C to cancel.
Return to the shutdown mode display.
You can execute a general reset command to return to the factory settings:
- the default configuration settings
- the default set-point temperatures, Heating Mode - Comfort: 19°C, Economy: 16°C
Cooling mode - Comfort: 23°C, Economy: 28°C
- the default schedule (Comfort mode from 6am to 11pm).
10 seconds
Cancel
Confirmation