- 13-

Automatic mode temperature display option

Enter your desired setting using the + or - buttons.
Press OK to confirm and move on to menu CF03

Setting the comfort temperature in heating mode

Enter your desired setting using the + or - buttons.
Press OK to confirm and move on to menu CF04

- 12 -

Correcting the temperature measured

IMPORTANT: In order to change this setting, the unit has to have been running for at
least 2 hours beforehand.

If there is a difference between the actual temperature (taken with a thermometer) and the
temperature measured and displayed by the unit, the CF01 function can be used to com-
pensate for the difference by adjusting the sensor's readings.

Example:
If the temperature displayed by the unit
is 19°C and the temperature measured
is 20°C, add 1°C to the display
then confirm by pressing OK.

Enter your desired setting using the + or - buttons
Press OK to confirm and move on to menu CF02

CF0 1

Correction possible from -4°C to + 4°C in increments of 0.1°C.
Press the + or - buttons to make changes, and confirm with the OK
button to move on to the next setting

CF02

0

Continuous set-point temperature display (by default).
With this option, press i to display the room temperature.

1

Continuous room temperature display.
With this option, press i to display the set-point temperature.

CF03

0

Comfort temperature set by the TYBOX (by default)

1

Comfort temperatures set by each radiator
or convector. In this option the screen displays ConF.