CRS-200 Redundancy Switch

Remote Control

Rev. 1

B–11

Parameter

Type

Command

(Instruction

Code and

qualifier)

Arguments for

Command or

Response to

Query

Description of arguments

(note that all arguments are ASCII numeric codes, that is,

ASCII codes between 48 and 57)

Response to Command

(target to controller)

Query

(Instruction Code

and qualifier)

Response to query

(target to

controller)

C being the fault code, where the value depends on fault
type:
Switch codes are 1 to D, defined the same as FLT string.
Modem codes are 1= Unit, 2= Rx traffic, 3= Tx traffic
Info codes are: 0= Power off, 1= Power on, 2= Log cleared
If there are no new events, the unit replies with RNE? If
fewer than 5 events remain, the last positions are zero

details of
arguments)

Retrieve
Number of
unread
Stored
Events

N/A

2 bytes,
numerical

Query only.
Switch returns the number of Stored Events which remain
unread, in the form xx. Note: This means unread over the
remote control – viewing the stored events from the front
panel of the modem does not affect this value. Example
reply: NUE=98

N/A

NUE?

NUE=xx (see
description for
details of
arguments)

Local/
Remote
Status

LRS=

1 byte, value of0
or 1

Command or query
Sets or queries the local/remote status of the switch:
0 = local
1= remote

LRS= (message ok)
LRS? (received ok, but
invalid arguments found)

LRS?

LRS=x (see
description for
details of
arguments)

Serial
Number

SNO=

4 bytes
numerical 0000
to 9999

Command portion is FACTORY USE ONLY. Used to set
or Query the units 4 digit serial number.
Unit returns its S/N, in the form xxxx.
Example: SNO=1765

SNO= (message ok)
SNO * (message ok, not
permitted in current
mode

SNO?

SNO=xxxx (see but
description for
details of
arguments)

Software
Revision

N/A

4 bytes,
numerical

Query only.
Unit returns the value of internal software revision installed
in the unit, in the form x.xx
Example: SWR=1.03 (Ver 1.03)

N/A

SWR?

SWR=x.xx
(see description for
details of
arguments)

Equipment
ID

N/A

4 bytes,
numerical

Query only.
Switch returns information concerning the equipment
identification, with only a base switch “S200” currently in
use

N/A

EID?

EID=xxxx
(see description for
details of
arguments)

Faults and
Status

N/A

13 bytes,
numerical

Query only.
Unit returns the current fault and status codes for the switch
itself, where each location in the string is either 0 for no
fault or 1 for faulted, and the positions are:
1 (leftmost) = RM remote comm problem
2/3 = +5v PSU-A under/over
4/5 = +5v PSU-B under/over
6/7 = +12v PSU-A under/over
8/9 = +12v PSU-B under/over
10/11 = -12v PSU-A under/over
12/13 (rightmost) = -12v PSU-B under/over

N/A

FLT?

FLT=xxxxxxxxx
xxxx (see
description for
details of arguments