Bronkhorst RS232 interface User Manual
Page 22
BRONKHORST
®
Page 22
RS232 interface
9.17.027
N
0A Parameter number (FBnr.) 10
Init mode
30
52
01010010
Parameter value 82, reset init mode
31
\r
Carriage Return
End
32
\n
Line Feed
Total String
:1D0301800A4081C500000000C63F800000C7000000004800000000000A52\r\n
Answer by node 3
Nr
Byte
Description
Description per block
0
:
Start character
Start
1
04
Fixed message length 4.
2
03
Node address
3
00
Command status
4
00
Status ok.
Status
5
1C
Status ok, value points to end of send message.
6
\r
Carriage Return
End
7
\n
Line Feed
Total String
:040300001C\r\n
3.10.3 Request setpoint
Request setpoint from node 3 process 1, type integer.
Nr Byte
Layout
Description
Description per block
0
:
Start
1
06
Length 6
2
03
Node 3
3
04
Command read
4
01
00000001
C
00 Process not chained (return)
Process 1
P
01 Process 1 (return)
5
21
00100001
C
00 Parameter not chained (return)
Parameter index 1
Process 1
Parameter number 1
Setpoint
T
20 Parameter type ‘integer’ (return)
N
01 Parameter index 1 (return)
6
01
00000001
P
01 Process 1
7
21
00100001
T
20 Parameter type ‘integer’
P
01 Parameter number (FBnr.) 1 (setpoint)
8
\r
Carriage Return
End
9
\n
Line Feed
Total String
:06030401210121\r\n
Answer from node 3 process 1, type integer.
Nr Byte
Layout
Description
Description per block
0
:
Start
1
06
Length 6
2
03
Node 3
3
02
Command write
4
01
00000001
C
00 Process not chained
Process
P
01 Process 1 (receiving process)
5
21
00100001
C
00 Parameter not chained
Parameter index 1
Setpoint
T
20 Parameter type ‘integer’
N
01 Parameter index 1