Bronkhorst RS232 interface User Manual
Page 21
BRONKHORST
®
Page 21
RS232 interface
9.17.027
3.10.2 Sending chained parameters
Interface sends following parameters to module at node 3:
Process 0: INIT MODE (10), 64 = soft init
Process 1: POLYNOMIAL CONSTANT A (5), 0.0
Process 1: POLYNOMIAL CONSTANT B (6), 1.0
Process 1: POLYNOMIAL CONSTANT C (7), 0.0
Process 1: POLYNOMIAL CONSTANT D (8), 0.0
Process 0: INIT MODE (10), 82 = reset init mode.
Send chained parameters to node 3
Nr Byte Layout
Description
Description per block
0
:
Start
1
1D
Length 29
2
03
Node 3
3
01
Command write with status response
4
80
10000000
C
80 Process chained
Process 0
P
00 Process 0
5
0A
00001010
C
00 Parameter not chained
Parameter number 10
Value 64
Init mode
T
00 Parameter type ‘character’
N
0A Parameter number (FBnr.)10
6
40
01000000 Parameter value 64 set soft init mode
7
81
10000001
C
80 Process chained
Process 1
P
01 Process 1
8
C5
11000101
C
80 Parameter chained
Parameter number 5
Value 0.0
Polynomial constant A
T
40 Parameter type ‘float’
N
05 Parameter number (FBnr.) 5
9
00
Parameter value ‘float’ 0.0
10
00
11
00
12
00
13
C6
11000110
C
80 Parameter chained
Parameter number 6
Value 1.0
Polynomial constant B
T
40 Parameter type ‘float’
N
06 Parameter number (FBnr.) 6
14
3F
Parameter value ‘float’ 1.0
15
80
16
00
17
00
18
C7
11000111
C
80 Parameter chained
Parameter number 7
Value 0.0
Polynomial constant C
T
40 Parameter type ‘float’
N
07 Parameter number (FBnr.) 7
19
00
Parameter value ‘float’ 0.0
20
00
21
00
22
00
23
48
01001000
C
80 Parameter not chained
Parameter number 8
Value 0.0
Polynomial constant D
T
40 Parameter type ‘float’
N
08 Parameter number (FBnr.) 8
24
00
Parameter value ‘float’ 0.0
25
00
26
00
27
00
28
00
00000000
C
00 Process not chained
Process 0
P
00 Process 0
29
0A
00001010
C
00 Parameter not chained
Parameter number 10
Value 82
T
00 Parameter type ‘character’