This calculation method can be used to determine the K
v
-value of the main orifice of a control valve.
4.7.1 For gases
Determine desired ∆p across valve.
∆
p must be at least 20% of supply pressure, or in closed loop systems, of total pressure difference in loop.
If ∆p is 20-50% of supply pressure, use formula:
K
T
p p
v
vn
n
=
⋅
⋅
Φ
∆
514
2
ρ
under critical
If ∆P is 50-100% of supply pressure, use formula:
K
p
T
v
vn
n
=
⋅
⋅
Φ
257
1
ρ
overcritical
Units:
Φ
vn
= flow [m
n
3
/h]
p
1
= supply pressure [bara]
p
2
= downstream pressure [bara]
∆
p = pressure difference (p
1
- p
2
) [bard]
T = temperature [K]
ρ
n
= density [kg/m
n
3
]
The orifice diameter can be determined by: d= 7.6 K
v
[mm]
4.7.2 For liquids
K
p
v
v
=
⋅
Φ
∆
ρ
1000
Units:
Φ
v
= volume flow [m
3
/h]
ρ
= density at 20°C and 1 atm [kg/m
3
]
∆
p = delta p [bard]
The orifice bore diameter can be determined by:
d
K
v
=
7.6
[mm]
*
page 24
9.17.001