EP18160008 Technical Data
Technical data
EP18160008
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Number of inputs
14
25 pin SUBD socket
Nominal input voltage
24 V
DC
(15%/+20%)
Input filter
10 µs
"0" signal voltage
3...+5 V (EN 611312, Type 3)
"1" signal voltage
+11...+30 V (EN 611312, Type 3)
Input current
typically 3 mA (EN 611312, Type 3)
Module electronic supply
derived from control voltage Us
Module electronic current consumption
typically 120 mA
Sensor supply
derived from control voltage Us
Sensor current consumption
max. 0.5 A total, shortcircuit proof
Power supply connection
Feed: 1 x M8 plug, 4pin
Onward connection: 1 x M8 socket, 4pin
Process image
16 input bits
Electrical isolation
Control voltage/fieldbus: yes
Permissible ambient temperature during operation
25°C ... +60°C
0°C ... +55°C (according to cULus, see UL
Requirements)
Permissible ambient temperature during storage
40°C ... +85°C
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227
EMC resistance/emission
conforms to EN 6100062 / EN 6100064
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus
2.8.3
EP18160008 StatusLEDs
Fig. 16: EP18160008 StatusLEDs
LED display
LED
Display
Meaning
STATUS 18
Green illuminated
A signal (24 V) is present at a least one of the inputs for
channels 1 to 8
STATUS 916
Green illuminated
A signal (24 V) is present at a least one of the inputs for
channels 9 to 16
Us
off
The power supply voltage, Us, is not present
Green illuminated
The power supply voltage, Us, is present
Up
off
The power supply voltage, Up, is not present
Green illuminated
The power supply voltage, Up, is present
EP1xxx
27
Version 2.1.0