2 ep1111-0000 - technical data, 3 ep1111-0000 - process image – BECKHOFF EP1xxx User Manual
Page 18

Product overview
2.5.2
EP11110000 Technical Data
Technical data
EP11110000
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 socket (green)
Task within EtherCAT system
identification of any EtherCAT group in the EtherCAT
network
Number of ID switches
3
Positions per ID switch
10
Number of different IDs
999
Module electronic supply
derived from control voltage Us
Module electronic current consumption
typically 120 mA
Sensor supply
derived from control voltage, Us
Sensor current consumption
max. 0.5 A total, shortcircuit proof
Power supply connection
Feed: 1 x M8 plug, 4pin
Onward connection: 1 x M8 socket, 4pin
Process image
2 byte input data
Weight
app. 165 g
Permissible ambient temperature during operation
25°C ... +60°C
0°C ... +55°C (according to cULus, see UL
Requirements)
Permissible ambient temperature during storage
40°C ... +85°C
Vibration / shock resistance
conforms to EN 6006826 / EN 60068227
EMC resistance/emission
conforms to EN 6100062 / EN 6100064
Protection class
IP65, IP66, IP67 (conforms to EN 60529)
Installation position
variable
Approvals
CE, cULus
2.5.3
EP11110000 Process image
ID inputs
You will find input data of the ID switches under under ID Inputs.
Fig. 9: EP11110000, ID inputs
EP1xxx
18
Version 2.1.0