Table 53: forwarding delays – BECKHOFF ET1200 User Manual
Page 64

Electrical Specifications and Timings
III-54
Slave Controller
– ET1200 Hardware Description
Table 53: Forwarding Delays
Symbol
Parameter
Min
Average
Max
Units
t
Diff
Average difference processing delay minus
forwarding delay (without RX FIFO jitter)
between any two ports
20
ns
t
EE
EBUS port to EBUS port delay (FIFO size 7):
a) Through ECAT Processing Unit
(processing), Low Jitter off
b) Alongside ECAT Processing Unit
(forwarding), Low Jitter off
c) Through ECAT Processing Unit
(processing), Low Jitter on
d) Alongside ECAT Processing Unit
(forwarding), Low Jitter on
a) 140
b) 120
c) 150
d) 130
a) 150
b) 130
c) 155
d) 135
a) 160
b) 140
c) 160
d) 140
ns
t
EM
EBUS port to MII port delay (FIFO size 7):
a) Through ECAT Processing Unit
(processing)
b) Alongside ECAT Processing Unit
(forwarding)
a) 145
b) 125
a) 170
b) 150
a) 195
b) 175
ns
t
ME
MII port to EBUS port delay (FIFO size 7):
a) Through ECAT Processing Unit
(processing), Low Jitter off
b) Alongside ECAT Processing Unit
(forwarding), Low Jitter off
c) Through ECAT Processing Unit
(processing), Low Jitter on
d) Alongside ECAT Processing Unit
(forwarding), Low Jitter on
a) 255
b) 235
c) 265
d) 245
a) 280
b) 260
c) 290
d) 270
a) 305
b) 285
c) 315
d) 295
ns
t
MM
MII port to MII port delay
(FIFO size 7, TX Shift=00):
Through ECAT Processing Unit (processing)
280
305
335
ns
NOTE: Average timings are used for DC calculations.