beautypg.com

4 faults – BECKHOFF CX2100­09x4 User Manual

Page 81

background image

Error handling and diagnostics

Error code argument

The number of pulses indicates the position of the last Bus Terminal before the fault. Passive Bus Terminals,
such as a power feed terminal, are not included in the count.

In the case of some errors, rectification does not cause the power supply to leave the blink sequence. The
power supply can only be restarted by switching its supply voltage off and on again.

6.3

LEDs of the power supply unit (CX2100­0xx4) in E­bus
mode

After switching on, the power supply immediately checks the connected Bus Terminal configuration. If K­bus
terminals are detected, the error­free bootup is signaled by the red “I/O ERR LED” going out. If the “I/O ERR”
LED blinks, an error in the area of the terminals is indicated. The error code can be determined from the
frequency and number of blinks. This permits rapid rectification of the error.

Display

LED

Meaning

Us 24 V

Power supply for the CPU module. The LED lights
green if the power supply is correct.

Up 24V

Power supply for terminal bus. The LED lights green if
the power supply is correct.

L/A

off

E­bus not connected

on

E­bus connected / no data traffic

flashing

E­bus connected / data traffic on the E­bus.

6.4

Faults

Please also refer to the Safety instructions section.

Possible faults and their correction

Fault

Cause

Measures

no function after the Embedded PC
has been switched on

no power supply for the Embedded
PC 
other causes

1.Check the fuse
2. Measure voltage at connection,
check plug wiring, call Beckhoff
support

Embedded PC does not boot fully

Hard disk damaged (e.g. due to
switching off while software is
running), incorrect setup, other
causes

Check setup Call Beckhoff Support

Computer boots, software starts,
but control does not operate
correctly

Cause of the fault is either in the
software or in parts of the plant
outside the Embedded PC

Call the manufacturer of the
machine or the software.

CF card access error

Faulty CFast card, faulty CFast slot Use a different CFast card to check

the CFast slot Call Beckhoff
Support

Embedded PC only works partially
or temporarily

Defective components in the
Embedded PC

Call Beckhoff support

Please make a note of the following information before contacting Beckhoff service or support:

1. Precise device ID: CXxxxx­xxxx

2. Serial number

3. Hardware version

4. Any interfaces (N030, N031,  B110, ...)

5. TwinCAT version used

CX2100­09x4

81

Version 1.1