BECKHOFF CX210009x4 User Manual
Page 44
Commissioning
2. From the list of the manufacturers select Beckhoff and as the model Beckhoff CX210009xx.
3. Close the dialog with Finish and confirm with Apply. This will cause the UPS service to adopt the
settings and start the UPS service.
4. Then, on the BECKHOFF UPS configuration dialog, go to Alarm configuration.
5. Activate the following options (not absolutely essential).
Activate all notifications: This option will cause the operating system to send messages to the user
whenever the power fails (not available under NT 4.0).
Critical alarm: The alarm is triggered once the battery voltage has fallen to a certain level or once
battery operation has exceeded a certain time limit. This parameter must be set to "0" for the CX20x0
system. It can be set to 1 minute in exceptional cases.
Execute the following program at an alarm: This option can be used to execute an application when
an alarm is raised (only available under NT 4.0 if the Microsoft Task Scheduler is installed).
Activate the following options:
Minutes remaining for battery operation before critical alarm: This option can be used to specify
the battery operation time in minutes until the Critical alarm is triggered. The shutdown of the operating
CX210009x4
44
Version 1.1