Error handling and diagnostics

k_bus_request := TRUE;     (* Rücksetzen des Busses, wenn Fehler beseitigt, dann startet der Klemm­
bus wieder *)

....

In order for the controller and the registers to co­operate, they must be linked in the System Manager.

6.2

LEDs of the power supply unit (CX2100­0xx4) in K­bus
mode

After switching on, the power supply immediately checks the connected Bus Terminal configuration. If K­bus
terminals are detected, the error­free bootup is signaled by the red “I/O ERR LED” going out. If the “I/O ERR”
LED blinks, an error in the area of the terminals is indicated. The error code can be determined from the
frequency and number of blinks. This permits rapid rectification of the error.

Display

LED

Meaning

Us 24 V

Power supply for the CPU module. The LED lights
green if the power supply is correct.

Up 24V

Power supply for terminal bus. The LED lights green if
the power supply is correct.

K­BUS
RUN

K­bus diagnostics. The green LED lights up in order to
indicate fault­free operation. "Fault­free" means that
the communication with the fieldbus system is also
running.

K­BUS
ERR

K­bus diagnostics. The red LED flashes to indicate an
error. The red LED blinks with two different
frequencies.

Table 1: The I/O error LED blink code

fast blinking

Start of the error code

First slow sequence

Error code

Second slow sequence

Error code argument