BECKHOFF CX210009x4 User Manual
Page 79
Error handling and diagnostics
k_bus_request := TRUE; (* Rücksetzen des Busses, wenn Fehler beseitigt, dann startet der Klemm
bus wieder *)
....
In order for the controller and the registers to cooperate, they must be linked in the System Manager.
6.2
LEDs of the power supply unit (CX21000xx4) in Kbus
mode
After switching on, the power supply immediately checks the connected Bus Terminal configuration. If Kbus
terminals are detected, the errorfree bootup is signaled by the red “I/O ERR LED” going out. If the “I/O ERR”
LED blinks, an error in the area of the terminals is indicated. The error code can be determined from the
frequency and number of blinks. This permits rapid rectification of the error.
Display
LED
Meaning
Us 24 V
Power supply for the CPU module. The LED lights
green if the power supply is correct.
Up 24V
Power supply for terminal bus. The LED lights green if
the power supply is correct.
KBUS
RUN
Kbus diagnostics. The green LED lights up in order to
indicate faultfree operation. "Faultfree" means that
the communication with the fieldbus system is also
running.
KBUS
ERR
Kbus diagnostics. The red LED flashes to indicate an
error. The red LED blinks with two different
frequencies.
Table 1: The I/O error LED blink code
fast blinking
Start of the error code
First slow sequence
Error code
Second slow sequence
Error code argument
CX210009x4
79
Version 1.1