BECKHOFF CX210009x4 User Manual
Page 64
Commissioning
Name
Type
Description
Default value
BatteryCapacity
REG_DWORD
Remaining UPS battery capacity in percent.
This element can adopt a value between 0
and 100 (the value displayed is rounded up).
0
BatteryStatus
REG_DWORD
Current status of the UPS battery. This
element can adopt the following values:
• 0 := the battery status is unknown;
• 1 := the battery status is OK;
• 2 := the battery must be exchanged;
0
CommStatus
REG_DWORD
Status of communication with the UPS. This
element can adopt the following values:
• 0 := the communication with the UPS
has an unknown status;
• 1 := the communication with the UPS is
OK;
• 2 := the communication with the UPS
has been interrupted.
0
FirmwareRev
REG_SZ
Returns the UPS firmware version number as
a string.
""
SerialNumber
REG_SZ
Returns the UPS serial number as a string.
""
TotalUPSRuntime
REG_DWORD
The remaining UPS battery time in minutes.
0
UtilityPowerStatus
REG_DWORD
Returns the status of the power supply. This
element can adopt the following values:
• 0 := the status of the power supply is
unknown;
• 1 := the power supply is OK;
• 2 := a power failure has been detected;
0
TcPowerFailCnt
REG_DWORD
Power failure counter. The counter increments
every time a power failure is detected.
0
BatteryReplaceDate REG_SZ
Date of the last battery change. The date can
be set with a command in the Beckhoff UPS
Configuration dialog > Device
Configuration…. Implemented in the UPS
software v3.0.0.8 and higher.
""
TcChargeFlags
REG_DWORD
Battery charge and status flags. This element
can adopt one or more values (bits) combined:
• 0 := unknown status (all bits are zero)
• 1 := charge status "High" (bit 0 is set);
• 2 := charge status "Low" (bit 1 is set);
• 4 := charge status "Critical" (bit 2 is set);
• 8 := charge status "Charging" (bit 3 is
set);
• Bit 4 6 reserved;
• 128 := No battery connected/found (bit 7
is set);
• 256 := UPS fan error (bit 8 is set);
• Bit 9 is reserved;
• 1024 := Battery change interval service
has expired (bit 10 is set). Implemented
in the UPS software v3.0.0.8 and
higher.
• Bit 11 31 reserved;
0
CX210009x4
64
Version 1.1