BECKHOFF CX210009x4 User Manual
Page 66
Commissioning
Name
Type
Description
Default value
Vendor
REG_SZ
Name of UPS manufacturer
"(none)"
Model
REG_SZ
UPS model designation
""
RunTaskEnable
REG_DWORD
Activates/deactivates the configuration of the
Task Scheduler shutdown task:
• 0 := deactivated;
• 1 := activated;
• other values are not permissible;
0
TaskName
REG_SZ
Name of the Task Scheduler shutdown task.
The Beckhoff UPS Configuration dialog
generates a shutdown task with the name:
"UPS System Shutdown Program".
""
TaskFolder
REG_SZ
Path to the folder containing the Task
Scheduler shutdown task. Implemented in the
UPS software v3.0.0.10 and higher. An empty
string represents the root folder.
""
TaskCompatibility
REG_DWORD
Task Scheduler v1.0 compatibility settings.
Implemented in the UPS software v3.0.0.10
and higher:
• 0 := automatic, uses the latest Task
Scheduler interface version
(at present v2.0);
• 1 := explicitly the Task Scheduler v1.0 is
to be used;
• 2 := explicitly the Task Scheduler v2.0 is
to be used;
• other values are not permissible;
0
RunTaskWait
REG_DWORD
Maximum running time (execution time) of the
shutdown task in seconds. Following the
expiry of this time the shutdown task is
stopped and the shutdown is continued.
Implemented in the UPS software v3.0.0.8
and higher and only under Windows Vista,
W7, WES 7 (32 and 64bit). With older
operating systems this time cannot be
changed and is fixed at 30 seconds.
30
ShutdownOnBatter
yEnable
REG_DWORD
Activates/deactivates the shutdown of the
operating system on a critical alarm:
• 0 := deactivated;
• 1 := activated;
• other values are not permissible;
1
ShutdownOnBatter
yWait
REG_DWORD
Maximum running time on battery voltage
before the critical alarm in minutes. This
element can adopt a value of between 0 and
720. Other values are not permissible.
2
NotifyEnable
REG_DWORD
Activates/deactivates the powerfail messages
to the loggedin user:
• 0 := deactivated;
• 1 := activated;
• other values are not permissible;
0
TurnUPSOffEnable REG_DWORD
Activates/deactivates the switchingoff of the
UPS output voltage after the shutdown:
• 0 := deactivated;
• 1 := activated (switches off);
1
CX210009x4
66
Version 1.1