beautypg.com

BECKHOFF CX2100­09x4 User Manual

Page 45

background image

Commissioning

system is only initiated once the alarm has been triggered. This option should be selected in order to
protect the battery. Set the “Battery time” to 2 minutes, for example. The permitted values lie between 0
and 720 minutes. The system will be shut down once this time has elapsed after a power failure. This
option corresponds to the same option that can be set in the standard UPS dialog, with the difference
that the shorter times of 0 and 1 minute can also be set.
Switch off UPS: If this option is selected, the UPS will switch off its own outputs after shutdown in order
to save the battery. This option also corresponds to the same option that can be set via the standard
UPS dialog. Default: Activated!.
Delay time for switching off the UPS [s]: After this delay the system should have shut down, and the
UPS switches its outputs off in order to save the battery. Must be set to "0" for the CX2100­09xx.

6. Close the dialog with OK, and then click Apply.

ð The configuration is thus completed.

CX2100­09x4

45

Version 1.1