Decs-200n operating mode information category c5, Decs-200n setpoints information category c6 – Basler Electric IDP-800 User Manual
Page 53

9437600990 Rev F
47
Register
Data Description
Access
Data Format
47306
Protection status bit flags (0 = clear, 1 = condition present):
b0=failed to build up, b1=build-up activated, b2= power input
failure, b3 = crowbar activated, b4 - b15 are unassigned.
R-
UI16
47307
Annunciation status bit flags (0 = clear, 1 = condition present)
b0=failed to build up, b1=build-up activated, b2= power input
failure, b3 = crowbar activated, b4– b15 are unassigned.
R-
UI16
DECS-200N Operating Mode Information Category C5
Category C5 holding register assignments and descriptions are listed in Table 7.
Table 7. DECS-200N Operating Mode Information Category C5
Register
Data Description
Access
Data Format
47571
Operating mode ( 0=OFF/ 1=PF/ 2=VAR)
R
UI16
47572
Unit mode status (1=START, 0=STOP)
R
UI16
47573
Control mode status (1=FCR, 2=AVR)
R
UI16
DECS-200N Setpoints Information Category C6
Category C6 holding register assignments and descriptions are listed in Table 8.
Table 8. DECS-200N Setpoints Information Category C6
Register
Data Description
Access
Data Format
47621-22
FCR mode (field current) setpoint
RW
R32_23
47623-24
AVR mode (generator voltage) setpoint
RW
R32_23
47625-26
Var mode setpoint in kvar
RW
R32_23
47627-28
PF mode setpoint
RW
R32_23
47699-700
FCR minimum setpoint
R-
R32_23
47701-02
AVR minimum setpoint
R-
R32_23
47703-04
Var minimum setpoint in kvar
R-
R32_23
47705-06
PF minimum setpoint
R-
R32_23
47707-08
FCR maximum setpoint
R-
R32_23
47709-10
AVR maximum setpoint
R-
R32_23
47711-12
Var maximum setpoint in kvar
R-
R32_23
47713-14
PF maximum setpoint
R-
R32_23
IDP-800
Modbus™ Communication