Decs-200, decs-250, and decs-250n register tables – Basler Electric IDP-800 User Manual
Page 50

44
9437600990 Rev F
Register
Data Description
Access
Data Format
47727
Virtual toggle switch for changing control mode from comm.
Port between AVR and FCR:
0 = no change / 1 = change state.
Holding register 47573 contains Control mode status.
W-
UI16
47728
Switch for changing operating mode via comm. port to one of
three modes.
0=OFF / 1=PF / 2=var.
Holding register 47571 contains Operating mode status.
To change the operating mode in the AVR, it is necessary to
pass the register 47729 at 1
W-
UI16
47729
Load new operation mode to the AVR
0= No change ; 1=change
W-
UI16
47730
Raise input enable status from comm. port:
0 = Off / 1 = On
W-
UI16
47731
Lower input enable status from comm. port:
0 = Off / 1 = On
W-
UI16
DECS-200, DECS-250, and DECS-250N Register Tables
Three categories of DECS-200, DECS-250, and DECS-250N information can be accessed through the
IDP-800 using the Modbus communication protocol: C2 (metering), C5 (operating modes), and C6
(setpoints).
DECS-200, DECS-250, and DECS-250N Metering Information Category C2
Category C2 holding register assignments and descriptions are listed in Table 3.
Table 3. DECS-200/DECS-250/DECS-250N Metering Information Category C2
Register
Data Description
Access
Data Format
47257-58
Average of the 3 rms line-to-line voltages
R-
R32_23
47259-60
Phase B generator current in amps
R-
R32_23
47261-62
Generator apparent power in kVA
R-
R32_23
47263-64
Generator real power in kW
R-
R32_23
47265-66
Generator reactive power in kvar
R-
R32_23
47267-68
Power factor
R-
R32_23
47269-70
Generator frequency in hertz
R-
R32_23
47271-72
Bus frequency in Hz
R-
R32_23
47273-74
RMS bus voltage in volts
R-
R32_23
47275-76
Field voltage in volts
R-
R32_23
47277-78
Field current in amps
R-
R32_23
47283-84
Auxiliary input in volts (PSS input)
R-
R32_23
47287-88
Null balance (tracking error) in percent
R-
R32_23
47295
Status of the Front panel LEDs (bit flags, where 0=off, 1=on for all
LEDs except Null Balance and Internal Tracking which are
reversed): b0=Null Balance, b1=Tracking, b2=Pre-position,
b3=Upper Limit, b4=Lower Limit, b5=Edit, b6-b15=unassigned
R-
UI16
47296
Voltage matching status: 0=off / 1=on
R-
UI16
47297
Protection status bit flags (0=clear, 1=condition present):
b0=field overvoltage, b1=field overcurrent, b2=gen. Undervoltage,
b3=gen. overvoltage, b4=underfrequency, b5=in OEL, b6=in UEL,
b7=in FCR mode, b8=loss of sensing voltage, b9=setpoint at
lower limit, b10=setpoint at upper limit, b11=gen. failed to build
R-
UI16
Modbus™ Communication
IDP-800