Constant-voltage mode -6 – AMETEK SGA Series User Manual
Page 88

Installation
Sorensen SGA Series
4-6
M550129-01 Rev AG
8. Verify that the unit produces 100%
0.8% of rated output current. If
necessary, adjust R33 for 100% of rated output current through the shunt.
9. Set the current programming source for 0.5 V
1 mV.
10. Verify that the unit produces 10%
0.8% of rated output current. If
necessary, adjust R47 for 10% of rated output current through the shunt.
11. Repeat the steps above as needed to obtain the required accuracy.
4.3.2 CONSTANT-VOLTAGE MODE
1. Disconnect AC mains power to the unit. Remove the current shunt from
the output and verify that there is no load attached.
2. Remove the precision meter leads from the current shunt and apply them
across the output terminals.
3. Setup the SGA Series unit to operate with remote voltage programming
using an external 0-5 VDC voltage-source, as shown in Figure 3-16 in
Section 3.6.2. Ensure that Pins J1-5 and J1-6 are jumpered to enable the
output.
4. Program the output current, with the front panel control or remote
interface, to 100% of rated output current.
5.
Apply AC power, turn the unit on, and press “Output On” button to enable
the output (see Section 3.1.1).
6. Set the voltage programming source to 5.0 V
1 mV.
7. Verify that the unit produces 100% ±0.25% of rated output voltage. If
necessary adjust R39 for 100% of rated output voltage.
8. Set the voltage programming source to 0.5 V ±1 mV.
9. Verify that the unit produces 10% ±0.25% of rated output voltage. If
necessary adjust R35 for 10% of rated output voltage.
10. Repeat the steps above as needed to obtain the required accuracy.
11. Remove all connections to the remote analog control connector (J1),
except the jumper between Pins J1-5 and J1-6; ensure that they are
jumpered to enable the output, and allow front panel control.