Sorensen SGA Series

Installation

M550129-01 Rev AG

4-3

4.2.1

CONSTANT-CURRENT MODE

1. Setup the SGA Series unit to operate with remote current programming

using an external 0-5 VDC voltage-source, as shown in Figure 3-14 in
Section 3.5.2. Ensure that Pins J1-5 and J1-6 are jumpered to enable the
output.

2. Connect a precision current shunt across the output of the power supply,

and attach a precision meter across the shunt Kelvin terminals. (see
Section 4.1.2 ).

3. Attach a precision meter in parallel with the current programming

voltage-source.

4. Set the current programming source to 0.0 V ±1 mV.

5. Program the output voltage, with the front panel control or remote

interface, to 100% of rated output voltage

6. Apply AC power, turn the unit on, and press the "Output On" button to

enable the output (see Section 3.1.13.1.1).

7. Set the current programming source to 5.0 V ±1 mV.

8. Verify that the unit produces 100% ±0.8% of rated output current. If

necessary, adjust R69 for 100% of rated output current through the shunt.

9. Set the current programming source for 0.5 V ±1 mV.

10. Verify that the unit produces 10% ± 0.8% of rated output current. If

necessary, adjust R55 for 10% of rated output current through the shunt.

11. Repeat the steps above as required to obtain the required accuracy.

4.2.2 CONSTANT-VOLTAGE MODE

1. Disconnect the AC mains power to the unit. Remove the current shunt

from the output and verify that there is no load attached.

2. Remove the precision meter leads from the current shunt and apply them

across the output terminals.

3. Setup the SGA Series unit to operate with remote voltage programming

using an external 0-5 VDC voltage-source, as shown in Figure 3-16 in
Section 3.6.2. Ensure that Pins J1-5 and J1-6 are jumpered to enable the
output.