CIRCUTOR AR5L Series User Manual
Page 38
![background image](https://www.manualsdir.com/files/767739/content/doc038.png)
38
6.1.2.4.- PARAM: Choosing the parameters to be saved
As said before, parameters to be saved in memory are user-definable when
working with STD files.
Pressing [ENTER] previously user-defined parameters are automatically
validated.
- To modify:
Place over the desired parameter with keys [
6
6
6
6], [5
5
5
5], [8
8
8
8] or [3
3
3
3].
Pressing [SET] the state of the parameter switches. Parameters to be
saved are on a black background, and the ones to be not save are on a
white background.
Placing over the text Inst (Instantaneous values) and pressing [SET], you
can now select the maximum values to be saved (MAX).
Placing over the text Max (Maximum values) and pressing [SET], you can
now select the minimum values to be saved (MIN).
Placing over the text MIN (Minimum values) and pressing [SET],you can
now select the parameters of harmonics that will be kept. Including the
number of harmonics(30 or 50), V and I for each phase and neutral current
(only in AR5-L model)
Press [ENTER] to validate the choice or [ESC] to exit with no modification.
Note:
- In case that have been selected some not-compatible parameters with the
active measuring circuit, when exiting Setup, analyzer will warn the user
about this fact and will automatically unselect such wrong parameters.
- If values the parameters to be stored are changed, when exiting setting
actions, the display will show:
“Error: New file should be created”
This message is shown since the change of parameters in an already existing file
is not allowed. Follow these instructions to change the parameters of a file:
1. If you want to keep the file name.
• Stop analyzer data recording process: SET -> RUN -> Stop.
• Exit SETUP.
• Delete the existing file: SET -> FILES -> DELETE.
• Modify the parameters to be saved: SET -> RECORD -> PARAM
• Enable the analyzer data recording process: SET -> RUN -> Run
• Exit SETUP.
2. If you want to change the file name.
• Change the file name: SET -> RECORD -> NAME.
• Modify the parameters to be saved: SET -> RECORD -> PARAM
• Exit SETUP.