beautypg.com

Wiring outputs, Schematic diagram of si5580 output circuit plc, Si5580 – Applied Motion Si5580 User Manual

Page 15

background image

-15-

Wiring Outputs

Before we discuss the output conditions, we need to talk about the circuitry. All three Si5580 outputs

are optically isolated. That means that there is no electrical connection between the indexer-drive and

the output terminals. The signal is transmitted to the output as light. What you “see” is a transistor

(NPN type) that closes, or conducts current, when the output is “low”. When the output is high, the

transistor is open.

Note: At power-up, the Si5580 sets all three programmable outputs high (open circuit).

Since there is no electrical connection to the Si5580, you must provide the source of current and

voltage, typically from a power supply. You must also limit the current to less than 100 mA so that the

output transistor is not damaged. You would normally use a resistor for this, but some loads (such as

PLC inputs) limit the current automatically.

The diagram below shows how to connect an Si5580 output to an optically isolated PLC input.

Schematic Diagram of Si5580 Output Circuit

PLC

COMMON

INPUT

Si5580

OUTPUT-

OUTPUT+

12-24 VDC

Power Supply

+

330W

+5V

OUT1–

OUT1+

Si5580

Controller Chip

inside Si5580

The maximum voltage between any pair of + and - output terminals is 24

volts DC. Never connect AC voltages to the Si5580 output terminals. Maxi-

mum current is 100 mA per output.