Dimensions – ABUS Technologies A9696 Series Universal Controller User Manual
Page 5

ABUS TECHNOLOGIES INC.
5
A9696
2.2 Technical Parameters
Dimensions:
96 x 96 x 92 mm. Weight: 330 g
Front panel:
IP65, Polycarbonate UL94 V-2.
Back panel:
IP30, ABS+PC UL94 V-0
Panel cut-out:
93 x 93 mm (+0.5 -0.0 mm)
Terminal connection:
24 screws accepting 6.3 mm fork lugs
Power:
85 to 265 Vac/dc, 50/60 Hz. Max. Consumption: 3 VA
Environmental conditions:
0 to 55 C, humidity: 20 to 85 %
Installation category II, pollution degree 2. Altitude < 2000 m
Keyboard selection of input type
Internal resolution:
19500 levels
Display resolution:
12000 levels (from -1999 to 9999)
Input sample rate:
5 per second
Accuracy:
Thermocouples J, K and T: 0.25 % of span 1 ºC
Thermocouple N, R, S: 0.25 % of span 3 ºC
Pt100, 4-20 mA, 0-50 mV, 0-5 Vdc: 0.2 % of span
Input impedance:
0-50 mV, Pt100 and T/C: >10M
0-5 V: >1 M
4-20 mA: 100
Pt100 measurement: DIN 43760 standard (=0.00385). Excitation current: 170 A. 3-wire
circuit, cable resistance compensation.
Analog output:
0-20 mA or 4-20 mA, 1500 levels, 550 max.
Two SPDT relays:
3 A / 250 Vac (3 A / 30 Vdc);
Two SPST relays:
3 A / 250 Vac (3 A / 30 Vdc);
Isolated 0-20 mA or 4-20 mA control output or PV or SP retransmission, 1500 level resolution,
550 max. Load;
Logic pulse for SSR drive:
0 or 20 mA;
Any of the above can be selected as the main control output and the remaining outputs can
be set as alarms;
Programmable PWM cycle from 0.5 sec. and 100 sec.;
Start up 3 seconds after power up;
Up to 4 alarms can be set with 9 distinct functions for each one.
2 Timing alarms, programmable from 0 to 6500 sec., with advanced functions, ideal for servo-
positioning.
Independent power-up inhibition of the 4 alarms.
Programmable hysteresis for the 4 alarms.
3. DIMENSIONS
PANEL
DIMENSION
CODE
PANEL
DIMENSION
CASE DIMENSION
HOLE
CUTOUT
DIMENSION
W
H
W
H
D
W
H
A9696
96
96
91
91
100
93
923