Before executing the program the controller waits for PV to reach the first set point SP0 if PtoL
is different than zero. Should any power failure occur, when the controller resumes at the beginning of
the segment that it was previously executing.
Event codes for ramp and soak
CODE
ALARM 1
ALARM 2
ALARM 3
ALARM 4
0
1
X
2
X
3
X
X
4
X
5
X
X
6
X
X
7
X
X
X
8
X
9
X
X
10
X
X
11
X
X
X
12
X
X
13
X
X
X
14
X
X
X
15
X
X
X
X
7.8 Serial Communication
An optional RS485 serial communication interface is available which allows up
to 247 controllers in a network to communicate to a master device.
7.5.1 RS485
Compatible signals with RS485 standard;
Two-wire connection from master to up to 247 slave controllers in a multi-drop bus;
Maximum communication distance: 1000 meters;
7.5.2 General Characteristics
Optically isolated serial interface
Programmable Baud rate: 1200, 2400, 4800, 9600 or 19200 bps.
Data Bits: 8
Parity: None
Stop Bits: 1