ABUS Technologies A9696 Series Universal Controller User Manual
Page 14

ABUS TECHNOLOGIES INC.
14
A9696
7.2 Input Type Selection
Select the input type (in parameter “tYPE”) from Table below.
TYPE
CODE
CHARACTERISTICS
J
0
Range: -50 to 760 °C (-58 to 1400 ºF)
K
1
Range: -90 to 1370 °C (-130 to 2498 ºF)
T
2
Range: -100 to 400 °C (-148 to 752 ºF)
N
3
Range: -90 to 1300 °C (-130 to 2372 ºF)
R
4
Range: 0 to 1760 °C (32 to 3200 ºF)
S
5
Range: 0 to 1760 °C (32 to 3200 ºF)
Pt100
6
Range: -199.9 to 530.0 °C (-328.0 to 986.0 ºF)
Pt100
7
Range: -200 to 530 °C (-328 to 986 ºF)
4-20 mA
8
J Linearization Programmable range: -110 to 760 °C
4-20 mA
9
K Linearization Programmable range: -150 to 1370 °C
4-20 mA
10
T Linearization Programmable range: -160 to 400 °C
4-20 mA
11
N Linearization Programmable range: -90 to 1370°C
4-20 mA
12
R Linearization. Programmable range: 0 to 1760 °C
4-20 mA
13
S Linearization Programmable Range: 0 to 1760 °C
4-20 mA
14
Pt100 Linearization Prog. Range: -200.0 to 530.0 °C
4-20 mA
15
Pt100 Linearization Prog. Range: -200 to 530 °C
0-50 mV
16
Linear. Programmable indication -1999 to 9999
4-20 mA
17
Linear. Programmable indication -1999 to 9999
0 to 5Vdc
18
Linear. Programmable indication -1999 to 9999
4-20 mA
19
Square Root Extraction
7.3 Output and Digital Inputs Configuration
The controller input/output channels can assume multiple functions, depending on
configuration: control output, alarm output, digital output, digital input, and PV or SV analog
retransmission. These channels are identified as I/O1, I/O2, I/O3, I/O4, I/O5 and I/O 6. The basic
controller model comes loaded with:
I/O1 and I/O2
- Relay output SPDT;
I/O3 and I/O4
- Relay output SPST;
I/O5
- Analog output (0-20 or 4-20 mA), pulse, digital I/O;
I/O6
- Digital Input
The function code of each I/O can be selected among the options on Table 2. Only valid
function codes are displayed for each I/O (for example, I/O1, which is a relay, can be configured with