functions 0 to 5 only; on the other hand, I/05 can perform all 16 functions). The description for the
functions follows:
CODE 0:
No function -
The I/O channel programmed with code 0 will not be used
by the controller. It is available to be used by serial
communication as digital output.
CODES 1 to 4:
Alarm output -
Available for all I/O channels. The selected channel can be
used as output to Alarms 1 to 4.
CODE 5:
PWM control output - Available for all I/O channels.
CODE 6:
Digital input -
Available for I/O5 and I/O6 channels and key
F
.
Closed: Manual control
Opened: Automatic control
I/O channel functions
CODE
I/O TYPE
I/O FUNCTION
0
Digital Output
Digital Output to be set by the serial comm.
1
Digital Output
Alarm 1 Output
2
Digital Output
Alarm 2 Output
3
Digital Output
Alarm 3 Output
4
Digital Output
Alarm 4 Output
5
Digital Output
PWM Control Output
6
Digital Input
Automatic/Manual mode change
7
Digital Input
Run/Stop mode change
8
Digital Input
Select Remote Set Point Input
9
Digital Input
Executes/Holds selected ramp and soak profile
10
Digital Input
Enable/Disable R&S profile 1 selection
11
Analog Output
0 ~ 20mA Analog control output
12
Analog Output
4 ~ 20mA Analog control output
13
Analog Output
0 ~ 20mA PV retransmission
14
Analog Output
4 ~ 20mA PV retransmission
15
Analog Output
0 ~ 20mA SP retransmission
16
Analog Output
4 ~ 20mA SP retransmission