7.1.6 I/O Cycle
PARAMETER
PROMPT PARAMETER DESCRIPTION
I
o 1
I/O 1 FUNCTION: Selects the I/O function to be used at I/O 1 (relay 1). Options 0 to
5 are possible for this output. Refer to Table 7.3 I/O channel functions for functions.
I
o 2
I/O 2 FUNCTION: Selects the I/O function to be used at I/O 2 (relay 2). Options 0 to
5 are possible for this output. Refer to Table 7.3 I/O channel functions for functions.
I
o 3
I/O 3 FUNCTION: Selects the I/O function to be used at I/O 3 (relay 3). Options 0 to
5 are possible for this output. Refer to Table 7.3 I/O channel functions for functions.
I
o 4
I/O 4 FUNCTION: Selects the I/O function to be used at I/O 4 (relay 4). Options 0 to
5 are possible for this output. Refer to Table 7.3 I/O channel functions for functions.
I
o 5
I/O 5 FUNCTION: Selects the I/O function to be used at I/O 5 (Analog Output).
Functions 0 to 15 are available (See Table 7.3 I/O channel functions). This option is
normally used for main control output or PV analog retransmission.
I
o 6
I/O 6 FUNCTION: Selects the I/O function to be used at I/O 6 (Digital Input).
Options 0, 6, 7, 8, 9 and 10 are possible for this input. Refer to Table 7.3 I/O
channel functions for functions.
f.fvnc
F
KEY FUNCTION: Selects the I/O function assigned to the front panel
F
key.
Available functions are:
0 - Key not used;
6 - Manual/Automatic control selection;
7 - Start/Stop the controller (RUN function);
8 - Select remote setpoint;
9 - Execute/Hold ramp and soak profile;
10- Enable/Disable ramp and soak profile 1;
7.1.7 Calibration Cycle
All input and output types are factory calibrated. This cycle should only be accessed by
experienced personnel. If in doubt do not press the
or
keys in this cycle.
PARAMETER
PROMPT PARAMETER DESCRIPTION
Inl(
INPUT LOW CALIBRATION: Sets the Process Variable low calibration (offset).
Several keystrokes at
or
might be necessary to increment one digit.
Inx(
INPUT HIGH CALIBRATION: Sets the Process Variable span calibration (gain).
ovll
OUTPUT LOW CALIBRATION: Sets the analog current output low calibration
(offset).
Ovx(
OUTPUT HIGH CALIBRATION: Sets the analog current output span calibration
(gain).
(j l
COLD JUNCTION OFFSET CALIBRATION: Sets the cold junction offset calibration.
Rsl(
REMOTE SET POINT LOW CALIBRATION: Sets the Remote Set Point low
calibration (offset). Several keystrokes at
or
might be necessary to increment
one digit.
Rsx(
REMOTE SET POINT HIGH CALIBRATION: Sets the Remote Set Point span
calibration (gain).