beautypg.com

Spectrum Controls 140 AUI 040 00sc User Manual

Page 8

background image

16-Channel Universal Analog Input Module

9

1.2

LEDs

The module has a front LED panel that includes 19 LEDs:

Ready LED - 1 Green LED indicates module’s self test has passed and is ready to communicate.

Active LED - 1 Green LED indicates BUS communication is established between the module and the rack.

Fault LED -1 Red LED indicates a module self test error, or fatal H/W error. A blink code will indicate the
type of self test error. Count the number of blinks before a pause to determine the error code in the table
below.

Blink # Fault
1

ROM CRC Error

2

EEPROM Error

3

RAM Error

4

Autocal Error

5

Watchdog Timer Error

6

CPU Error

7

DPM Error

Channel LED - 16 Green LEDs indicates the channel is enabled and a valid input signal level is present.
The LED is off if the channel is disabled. A blinking LED indicates that the channel has exceeded a range
limit.

1.3

Related Publications

Modicon Modsoft Programmer User Manual. 890 USE 115 00

• Modicon TSX Quantum Automation Series Hardware Reference Guide. 840 USE 100 00

• IEEE Std 518- 1977, Guide for the Installation of Electrical Noise Inputs to Controllers from External Sources

• IEEE Std 142- 1982, Recommended Practice for Grounding of Industrial and Commercial Power Systems

• Noise Reduction Techniques in Electronic Systems, by Henry W. Ott; published by Wiley-Interscience of New York in
1976