background image

Quantum Series 140 AUI 040 00sc

18

The register data formats are discussed in the following section.

4x

Configuration Word

3x + 0 Input Data Channel 1/9

3x + 1 Input Data Channel 2/10

3x + 2 Input Data Channel 3/11

3x + 3 Input Data Channel 4/12

3x + 4 Input Data Channel 5/13

3x + 5 Input Data Channel 6/14

3x + 6 Input Data Channel 7/15

3x + 7 Input Data Channel 8/16

The AUI 040 00sc multiplexes 16 channels of data into four groups of four channels. Each group can be
selected through the 4x Configuration Word or can automatically sequence through all four groups of chan-
nels.

Group 1 Chn 1-4

3x + 0 Input Data Channel 1/9

Group 2 Chn 5-8

3x + 1 Input Data Channel 2/10

3x + 2 Input Data Channel 3/11

Group 3 Chn 9-12

3x + 3 Input Data Channel 4/12

Group 4 Chn 13-16

3x + 4 Input Data Channel 5/13

3x + 5 Input Data Channel 6/14

3x + 6 Input Data Channel 7/15

3x + 7 Input Data Channel 8/16

3.4

Concept I/O Map Module Parameters:

Concept programming software does not implement zoom screens for ModConnect partner modules and
allows only direct editing of the I/O configuration parameters using 16 bit hex values. Spectrum Controls has
provided a software utility to simplify the configuration process. Refer to Section 3.5 for details.

From the Concept main screen, highlight the “configure” pull-down menu and choose “I/O Map.” In the I/O
Map screen insert the number for the correct “drop” and choose “edit.” Select the Spectrum Controls catalog
number that you wish to use from the list presented. When the screen appears, representing the Spectrum
module you have selected, highlight the parameters button. You must insert Hex values for registers #1, 2 and
3 to fully configure the module. The format that will instruct you on how to create the I/O map parameters is
listed below. For each of the parameters listed we have provided a detailed explanation in Chapter 2. Please
refer to detailed functional descriptions in the MODSOFT zoom screen discussions (Section 2.4). You must
go through each of the options below to establish the correct pattern for each of these three registers. Once
you have the bit pattern, then you can convert each to a four-digit Hex value that is used in the parameters
screen.

Configuration Register 1

Group 1

Group 2

Group 3

Group 4

Ch. 1-4

Ch. 5-8

Ch. 9-12

Ch. 13-16

Zoom +10

Zoom +12

Zoom +14

Zoom +16