beautypg.com

Spectrum Controls 140 AUI 040 00sc User Manual

Page 39

background image

16-Channel Universal Analog Input Module

41

Range

Signed 16 bit**

Unsigned 16 bit

Unsigned 12 bit

DVM deg C

DVM deg F

Min

Max

Min

Max

Min

Max

Min

Max

Min

Max

RTD Pt 385

-32,767 32,767

0

65,535

0

4,095

-2,000

8,500

3,280

15,620

RTD Pt 385

-32,767 32,767

0

65,535

0

4,095

-2,000

8,500

3,280

15,620

RTD Pt 385

-32,767 32,767

0

65,535

0

4,095

-2,000

8,500

3,280

15,620

RTD Pt 385

-32,767 32,767

0

65,535

0

4,095

-2,000

8,500

3,280

15,620

RTD Pt 3916

-32,767 32,767

0

65,535

0

4,095

-2,000

6,600

3,280

11,660

RTD Pt 3916

-32,767 32,767

0

65,535

0

4,095

-2,000

6,600

3,280

11,660

RTD Pt 3916

-32,767 32,767

0

65,535

0

4,095

-2,000

6,600

3,280

11,660

RTD Pt 3916

-32,767 32,767

0

65,535

0

4,095

-2,000

6,600

3,280

11,660

RTD Nickel 618

-32,767 32,767

0

65,535

0

4,095

-600

2,500

-760

3,560

RTD Nickel 618

-32,767 32,767

0

65,535

0

4,095

-600

2,500

-760

3,560

RTD Nickel 618

-32,767 32,767

0

65,535

0

4,095

-600

2,500

-760

3,560

RTD Nickel 618

-32,767 32,767

0

65,535

0

4,095

-600

2,500

-760

3,560

RTD Copper 426

-32,767 32,767

0

65,535

0

4,095

1,000

2,600

1,480

5,000

RTD Nickel 672

-32,767 32,767

0

65,535

0

4,095

-800

2,600

1,120

5,000

RTD Nickel/Iron 518

-32,767 32,767

0

65,535

0

4,095

1,000

2,000

1,480

3,920

Thermocouple type J

-32,767 32,767

0

65,535

0

4,095

-2,100

7,600

-3,460

14,000

Thermocouple type K

-32,767 32,767

0

65,535

0

4,095

-2,700

13,700

-4,540

24,980

Thermocouple type T

-32,767 32,767

0

65,535

0

4,095

-2,700

4,000

-4,540

7,520

Thermocouple type E

-32,767 32,767

0

65,535

0

4,095

-2,700

10,000

-4,540

18,320

Thermocouple type R

-32,767 32,767

0

65,535

0

4,095

0

17,680

320

32,140

Thermocouple type S

-32,767 32,767

0

65,535

0

4,095

0

17,680

320

32,140

Thermocouple type B

-32,767 32,767

0

65,535

0

4,095

3,000

18,200

5,720

32,667*

Thermocouple type N

-32,767 32,767

0

65,535

0

4,095

0

13,000

320

23,720

* Thermocouple Type B readings are clipped at 32,767 counts fo rthe DVM and degF scales. Readings above 32,767 are
flagged as an over-range error.

** Same as 15bit + sign.

6.7 RTD and Thermocouple inputs.

Thermocouples convert temperature to very small voltages. The Quantum Universal module’s specifications
for thermocouple inputs assume the 50/60 Hz filter setting or the low speed (7.8 Hz 3dB, 28Hz stop freq) filter
is being used. These two filter settings are recommended for thermocouple inputs. Using the two faster filter
settings will provide a faster update rate, but with noise and accuracy degradation.

RTDs are resistance temperature detectors. RTDs convert temperature to resistance levels which the
quantum universal measures. In some cases the resistance change per degree is very small. The accuracy
specifications assume the 50/60 Hz filter or the low speed filter (7.8Hz 3db) is being used. These two filter
settings are recommended for RTD inputs.

Recommended filter settings for RTD and thermocouple inputs are listed below.

Filter

J, K, T, E, N

S, B, N

RTD

Thermocouple inputs

Thermocouple inputs

Inputs

Reject 50/60Hz Recommended

Recommended

Recommended

Reject 28Hz

Recommended

Recommended

Recommended

Reject 800 Hz Some accuracy

Not recommended

Minimal

degradation

accuracy degradation

Reject 6400Hz Do not use

Do not use

Not recommended