7.1

General Information

Review of the Module Setup Procedures in Section 2.1 is recommended prior to following the troubleshooting
steps below to help isolate the problem. The troubleshooting guide lists a variety of possible problems. Step
through each item on the list and verify whether or not the module is working. If a particular step is not
working, follow the corrective action listed.

STEP 1: Check module power and self test.

VERIFY: The controller module’s READY and RUN LED’s are on.

CORRECTIVE ACTION:

Insure that the rack’s power supply is connected properly and its PWR OK LED is on.
• Place the controller in run mode by using the Modsoft Start Command.
• If the rack’s power will not come up, or the system will not go into run mode, refer to the Quantum Automation Series

Hardware Reference Guide for more information.

STEP 2: Check module power and self test.

VERIFY: The module’s green READY LED is on. This indicates that the module has power and has
completed it functional self test.

CORRECTIVE ACTION:

• Check rack power, and reinstall the module in the rack.

STEP 3: Check the module’s fault LED.

VERIFY: The module’s red FAULT LED is off. This LED indicates a module hardware error.

CORRECTIVE ACTION:

• The module has a fatal hardware error. Contact your local distributor or Spectrum Controls Customer Satisfaction
Group listed at the back of this manual.

The module has a front LED panel that includes 19 LEDs:

Ready LED -

1 Green LED indicates module’s self test has passed and is ready to communicate.

Active LED -

1 Green LED indicates BUS communication is established between the module the rack.